Instructions

minals for the power connection. Fasten with 
3 Nm torque.

  •   The thermostat connection (if present) is a ¼” 

AMP-AWE spade connector.

 •   The compressor must be connected to earth 

with the 5 mm earth terminal screw.

8 – Filling the system

  •   Keep the compressor switched off.
 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. The charge must 
be as close as possible to the nominal system 
charge to avoid low pressure operation and ex-
cessive superheat. Never let the pressure on LP 
side exceed the pressure on HP side with more 
than 5 bar. Such pressure difference could 
cause internal compressor damage.

  •   Keep the refrigerant charge below the indica-

ted charge limits if possible. Above this limit; 
protect the compressor against liquid flood-
back with a pump-down cycle or suction line 
accumulator.

 •   Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant charge 

limit (kg)

SM/SZ 084, 090, 100

8.5

SM/SZ 110, 120

10

SM 112, 124, 147, SZ147

7.9

SM/SZ 115, 125

11

SM/SZ 148, 160, 161

12.5

SM/SZ 175, 185

13.5

SY/SZ 240

16

SY/SZ 380

20

SH / WSH 090

5.9

SH / WSH105, 120, 140, 

161, 184

7.9

SH 180, 240, 295, 300

13.5

SH 380

14.5

SH 485

17

 

9 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in com-
pliance with both generally and locally appli-
cable regulations and safety standards. Ensure 
that they are operational and properly set. 

 Check that the settings of high-pressure 

switches and relief valves don’t exceed the 
maximum service pressure of any system com-
ponent.

 •  A low-pressure switch is recommended to 

avoid vacuum operation. Minimum setting 
for SM/SY/SZ: 0.5 bar g. Minimum setting for 
SH / WSH: 1.5 bar g.

 •   Verify that all electrical connections are pro-

perly fastened and in compliance with local 
regulations.

 •  

When a crankcase heater is required, it 
must be energized at least 12 hours before 
initial start-up and start-up after prolonged 
shutdown for belt type crankcase heaters (6 

hours for surface sump heaters).

10 – Start-up

 •   Never start the compressor when no refrige-

rant is charged.

  •   All service valves must be in the open position.
  •   Balance the HP/LP pressure.
 •  

Energize the compressor. It must start 
promptly. If the compressor does not start, 
check wiring conformity and voltage on ter-
minals.

 •  Eventual reverse rotation can be detected 

by following phenomena; the compressor 
doesn’t build up pressure, it has abnormally 
high sound level and abnormally low power 
consumption. In such case, shut down the 
compressor immediately and connect the 
phases to their proper terminals. Most Dan-
foss scroll compressors are protected against 
reverse rotation either by an internal reverse 
rotation protection or by the external elec-
tronic protection module. They will shut off 
automatically. Only SH / WSH 090 to 184 and 
SM 112, 124, 147, SZ147 have no reverse rota-
tion protection. Prolonged reverse rotation 
will damage these compressors.

 •   If the internal overload protector trips out (SM/

SZ 084, 090, 100, 110, 112, 120, 124, 147, 148, 
161 and SH / WSH 090, 105, 120, 140, 161, 184), 
it must cool down to 60°C to reset. Depending 
on ambient temperature, this may take up to 
several hours.

 •   If the internal pressure relief valve is opened 

(SY/SZ 240, 300, 380 and SH 380, SH 485), the 
compressor sump will be warm and the com-
pressor will trip out on the motor protector.

11 – Check with running compressor

  •   Check current draw and voltage.
 •  Check suction superheat to reduce risk of 

slugging.

 •  Observe the oil level in the sight glass for 

about 60 minutes to ensure proper oil return 
to the compressor.

  •   Respect the operating limits.
  •    Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 
measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 
far as possible from the compressor. The com-
pressor must be operating during this process.

  •   Do not overcharge the system.
  •   Never release refrigerant to atmosphere.
 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

  •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

12 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.

To prevent system related compressor problems, 
following periodic maintenance is recommended:
 •    Verify that safety devices are operational and 

properly set.

  •    Ensure that the system is leak tight.
  •    Check the compressor current draw.
  •    Confirm that the system is operating in a way 

consistent with previous maintenance re-
cords and ambient conditions.

 •   Check that all electrical connections are still 

adequately fastened.

  •    Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compres-
sor shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial number 
with any claim filed regarding this product.
The product warranty may be void in following cases:
  •    Absence  of  nameplate.
 •   External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •    Compressor opened or returned unsealed.
 •   Rust, water or leak detection dye inside the 

compressor.

  •    Use of a refrigerant or lubricant not approved 

by Danfoss.

 •   Any deviation from recommended instruc-

tions pertaining to installation, application or 
maintenance.

  •    Use in mobile applications.
  •    Use in explosive atmospheric environment.
  •    No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 
and compressor oil should be recycled 
by a suitable company at its site.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on 

order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FRCC.EI.003.A6.02 - January 2014 

Copyright Danfoss Commercial Compressors - DSS - 01/14

Summary of Contents for SM Serires

Page 1: ...ish http instructions cc danfoss com Svenska Swedish Portugu s Portuguese Nederlands Dutch Gaeilge Irish Suomi Finnish Lietuviu kalba Lithuanian Latviesu valoda Latvian Eesti Estonian Elinika Greek Po...

Page 2: ......

Page 3: ...Instructions Sm Sy sz sh WSH Compressors Installation and servicing of the compressor by qualified personnel only Follow these instructions and sound refrigeration engineering practice relating to in...

Page 4: ...g the cir cuit against over current CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versions with thermostat SZ 1...

Page 5: ...rails Use the rigid spacers from the tandem mounting kit or the rigid spa cers delivered with dedicated tandem com pressors Slowly release the nitrogen holding charge through the schrader port Remove...

Page 6: ...may take up to several hours If the internal pressure relief valve is opened SY SZ 240 300 380 and SH 380 SH 485 the compressor sump will be warm and the com pressor will trip out on the motor protect...

Page 7: ...uctions Compresseurs Sm Sy sz sh WSH Toute op ration de montage et d entretien du compresseur doit exclusivement tre effectu e par un personnel qualifi Le montage la mise en service la maintenance et...

Page 8: ...SV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versions avec thermostat SZ 115 125 160 175 185 Ces compresseurs Danfoss sont fournis avec un thermostat unipolaire bilame situ danslesenro...

Page 9: ...d di s R duire progressivement la pression d azote interne via le raccord Schrader Retirer les joints pour braser les raccords Ro tolock Utiliser syst matiquement des joints neufs pour l assemblage R...

Page 10: ...arm Cela peut n cessiter plusieurs heures en fonction de la temp rature ambiante Si le d tendeur de pression interne est ouvert SY SZ 240 300 380 et SH 380 SH 485 le carter du compresseur sera chaud...

Page 11: ...C D A B A D B E C F 5 30 T C C T0 C R407C R404A R507A R22 R417A T C C T0 C 5 R134a T C C T0 C SZ 240 300 380 T C C T0 C SZ 240 300 380 R410A SH SM SY T C C T0 C SZ 084 185 T C C T0 C SZ 084 185 t c c...

Page 12: ...10 120 147 148 161 SH WSH 140 3 161 3 184 SH140 3 161 3 184 WSH140 3 161 3 184 Danfoss CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP S...

Page 13: ...ss SM SY SZ SH WSH 2 35 C 50 C 3 50 C 3 SZ SH WSH HFC CFC HCFC 4 SH WSH SM112 SM124 SM147 SZ147 1 80 Nm 1 1 4 90 Nm 1 3 4 110 Nm 2 1 4 130 Nm 5 SM 084 185 SY 380 SZ 084 185 SZ 380 SH 090 184 WSH 090 1...

Page 14: ...0 161 184 7 9 SH 180 240 295 300 13 5 SH 380 14 5 SH 485 17 9 SM SY SZ 0 5 bar g SH WSH 1 5 bar g 12 6 10 Danfoss SH WSH 090 184 SM 112 124 147 SZ147 SM SZ 084 090 100 110 112 120 124 147 148 161 SH W...

Page 15: ...C EI 003 A6 06 Danfoss Commercial Compressors 01 14 15 Istruzioni Compressori SM SY SZ SH WSH Seguire queste istruzioni e le corrette procedure relative a installazione messa in servizio manutenzione...

Page 16: ...hM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 versioni con termostato SZ 115 125 160 175 185 I compressori Danfoss sono dotati di termostato bimetallico monopolare a...

Page 17: ...alla valvola Schrader Rimuovere le guarnizioni prima della brasa tura dei raccordi rotolock Utilizzare nuove guarnizioni per il montaggio Collegare prima possibile il compressore al sistema per evitar...

Page 18: ...ecessarie diverse ore Se la valvola limitatrice della pressione inter na aperta SY SZ 240 300 380 e SH 380 SH 485 lo scarico del compressore si surriscalda ed il compressore si arresta su intervento d...

Page 19: ...01 14 19 Instrucciones Compresores Sm Sy sz sh WSH La instalaci n y el mantenimiento del compresor deben ser realizados nicamente por personal cualificado Siga estas instrucciones y las pr cticas de...

Page 20: ...miendautilizartambi nunaprotecci nadicionalexternaconrearmemanual CC F1 F1 KA KA KA HP LPS T1 T2 T3 KM DGT KS KS 1 2 M ThM KS KS KA KM KM LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185...

Page 21: ...carga de nitr geno a tra v s de la boquilla schrader Al soldar los conectores Rotolock retire las juntas Utilice siempre juntas nuevas para el mon taje Conecte el compresor al sistema lo antes po sibl...

Page 22: ...rir va rias horas Si se abre la v lvula de descarga de presi n in terna SY SZ 240 300 380 y SH 380 SH485 el c rter del compresor se calentar y el pro tector del motor parar el compresor 11 Comprobacio...

Page 23: ...mpressors 01 14 23 INSTRUKTION SCROLL Verdichter SM SY SZ SH WSH Installation und Wartung des Verdichters d rfen nur von qualifiziertem Fachpersonal durchgef hrt werden Diese Anleitung befolgen und be...

Page 24: ...M LLSV 180s TH F2 Q1 L1 L3 L2 A1 A2 A3 LP SM 115 125 160 175 185 Ausf hrungen mit Thermostat SZ 115 125 160 175 185 Diese Danfoss Verdichter verf gen ber ein bimetallisches SPST Ther mostat in den Mot...

Page 25: ...lter aus dem Tandem Einbausatz oder die starren Abstandhalter im Lieferumfang spezieller Tandem Verdichter verwenden Die Stickstofff llung langsam durch das Schraderventil ablassen Zum Hartl ten der R...

Page 26: ...et Lediglich die Verdichter SH WSH 090 184 und SM 112 124 und 147 SZ147 verf gen nicht ber einen integrierten Schutz vor falscher Drehrichtung Ein Betrieb mit falscher Drehrichtung von f hrt bei die s...

Page 27: ......

Page 28: ...oducts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the re...

Reviews: