Operating guide
Termix AT BTD
7.2 Other
7.2.1 Cold water meter fitting piece
The substation is equipped with a fitting piece for cold water meter.
Assembly of cold water meter:
1: Close ball valves
Close the ball valves on cold water, if there is water on the system.
2: Loosen nuts
Loosen the nuts on the fitting piece.
3: Remove fitting piece
Remove the fitting piece and replace it with the cold water meter.
Do not forget the gaskets.
4: Tighten connections
After mounting of the cold water meter remember to check and
tighten all threaded connections.
7.2.2 Siphon
Placed the Siphon directly under the Safety valve.
Ensure that the drainpipe has a minimum internal diameter of
32mm.