35 of 114
M-AP-001-EN Rev. Q
Chapter 5.0 General Specifications
5.1 Construction
• Compressor - Semi-hermetic design
• Main Housing - Dimensionally-stabilized aluminum
• Covers - High-impact, UV stabilized, flame-resistant polymer.
• Covers - High-impact, UV stabilized, flame- resistant polymer. TGS series is identified
by green cover.
• Shaft - High-strength alloy
• Impellers - High-strength aluminum
• Motor - Permanent magnet, synchronous, DC
• Bearings - Integrated, digitally-controlled, magnetic
• Compressor Control - Integrated, digital capacity control
• Enclosure - IP54 rating as per UL 984 requirement
• UL60335-2-34
5.2 Maximum Pressure
The maximum pressure that the compressor can operate is regulated directly by two control settings:
(1) Alarm Limit and (2) Trip Limit. It is also controlled by a Pressure Ratio alarm limit monitoring the
ratio between the Discharge and Suction Pressures.
Table 5-1 Discharge Pressure Alarm and Trip Settings
* In the TGS230/TTS300 compressors, the alarm and trip settings default to lower values of operation, which are
typically deemed appropriate for Water-Cooled conditions.
These values allow for adjustment for compressors placed in Air-Cooled applications, which can have
the value increased up to 1730 kPa(g)/250 PSIG for the Alarm and 1800 kPa(g)/260 PSIG for the Trip.
THIS PAGE INTENTIONALLY LEFT BLANK
Model
Alarm
Trip
kPa(g)
PSIG
kPa(g)2
PSIG3
TGS230ST*
1239
180
1299
188
TGS230MT*
1116
162
1176
171
TGS310
1240
180
1300
189
TGS490
1240
180
1300
189
TGS390
876
127
926
134
TGS520
876
127
926
134
TGH285
1510
218
1586
229
TTS300ST*
1190
173
1240
180
TTS300MT*
1190
173
1240
180
TTS350
1730
251
1800
261
TTS400
1190
173
1240
180
TTS700
1190
173
1240
180
TTH375
2016
292
2116
306
Summary of Contents for TGH Series
Page 8: ...8 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...10 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 34: ...34 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 38: ...38 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 46: ...46 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 54: ...54 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 56: ...56 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 58: ...58 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 78: ...78 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 88: ...88 of 114 M AP 001 EN Rev Q Figure 16 17 Suction Port All Models ...
Page 94: ...94 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 96: ...96 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...98 of 114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 108: ...108of114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 110: ...110of114 M AP 001 EN Rev Q THIS PAGE INTENTIONALLY LEFT BLANK ...