58 of 132
M-SV-001-EN Rev.E
Compressor Components
3.7.4.3 Inverter Removal
1. Isolate the compressor power as described
in the “Electrical Isolation of the Compressor”
section of this manual.
2. Recover the refrigerant from the compressor.
3. Remove the Soft Start Board.
4. Remove the Mains Input terminal and bus bars.
5. Remove the DC capacitor and bus assembly.
6. Remove the HV DC/DC Converter.
7. Disconnect the ribbon cable from the Inverter.
8. Remove the copper tubes that connect the
motor bus bars to the Inverter.
9. Remove the DC bus bars from SCRs (TT300/
TG230 only).
10. Disconnect the SCR gate connectors from the
SCRs (TT300/TG230 only).
11. Remove the screws that secure the Inverter
to the compressor main housing. See Figure 54
(Removing the Inverter).
12. Disconnect the SCR temperature sensor
connector.
13. Remove the SCR cooling manifold (TT350,
TT400, TT500, TT700, TG310, TG390, and TG520
only).
14. Carefully remove the Inverter and discard the
O-ring.
• • • CAUTION • • •
Removal of the Inverter mounting screws will release refrigerant. Isolation and recovery of the refrigerant must be performed by a
qualified service technician adhering to industry/ASHRAE standards.
Figure 54 - Removing the
Inverter (TT300/TG230
Shown)
3.7.4.2 Inverter
Installation
1. Clean the O-ring groove in housing.
2. Install the O-ring into the groove of the main
compressor housing.
3. Carefully install the Inverter.
4. Install the SCR cooling manifold (TT350, TT400,
TT500, TT700, TG310, TG390, and TG520 only).
5. Route the SCR temperature sensor cable under
the SCR cooling manifold.
6. Connect the SCR temperature sensor
connector to the cable harness.
7. Install Inverter screws in a diagonal sequence.
Torque to 6Nm (4.5 ft./lb.).
8. Leak test the compressor in accordance with
industry standard.
9. Evacuate compressor to appropriate pressure
and industry accepted standards.
10. Connect the SCR gate connectors to the SCRs
(TT300/TG230 only).
11. Install the DC bus bars to the SCRs (TT300/
TG230 only).
12. Install the copper tubes that connect to the
motor bus bars to the Inverter.
13. Connect the ribbon cable to the Inverter.
14. Install the HV DC/DC Converter.
15. Install the DC capacitor and bus assembly.
16. Install the Mains Input terminal and bus bars.
17. Install the Soft Start Module.
Summary of Contents for Turbocor TG230
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 4: ...4 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...61 of 132 M SV 001 EN Rev E Compressor Components Figure 56 Stator Thermistor R T Curve 1 ...
Page 120: ...120 of 132 M SV 001 EN Rev E THIS PAGE INTENTIONALLY LEFT BLANK ...