Table 5-4 Motor Fault Types
Table 5-5 Bearing Fault Types
5.2 Troubleshooting with the Service Monitoring Tools Software
The SMT software package can be used to view detailed compressor information for operational status
indications and troubleshooting procedures. Please refer to the Service Monitoring Tools User Manual
for the details on how to use the SMT software.
Compressor
Description
Motor Single Phase Overcurrent
Fault
Measured peak current value of any single phase to motor (from Inverter)
exceeds the fault limit.
DC Bus Overvoltage Fault
The measured DC bus voltage has exceeded the Maximum Bus Voltage
limit.
Motor High Current Fault
The motor current has exceeded Maximum Motor Current limit.
Inverter Error
Inverter reports a generic error or communication to BMCC is lost.
Bearing Fault Active
If a bearing fault type is present, then the Bearing Error fault is triggered.
This is not an actual fault, only an indication that a fault has occurred in the
bearing section.
Rotor Starting Torque Fault
Motor Current maximum has been exceeded during compressor start-up.
Low Inverter Current Fault
Measured current to motor (from Inverter) has not reached the Minimum
Power limit.
DC Bus Under/Over Voltage Fault
At 0 RPM: The measured DC Bus voltage is measured lower than the Soft
Start Bus Voltage limit.
24VDC Under/Over Voltage Fault
The measured 24VDC supply is outside the range of the low or high limit.
Low Motor Back EMF Fault
The calculated motor back EMF has fallen below the minimum Back EMF
limit.
EEPROM Checksum Fault
An error (checksum error) occurs reading the data table from the EEPROM.
Generator Mode Active
At greater than 0 RPM and DC bus voltage low, Generator mode is enabled,
switching the Inverter to rectifier function to maintain the DC bus voltage
until the shaft comes to a stop and delevitates.
SCR Ripple Voltage Fault
The DC bus voltage ripple exceeds the SCR Voltage Ripple Fault limit.
System in Startup mode
The compressor initialization has not finished. Please wait. Compressor is
resetting after a power cycle. This is a status message.
Bearing Status
Description
Startup Calibration Check Fault
During initialization, the bearing calibration data is checked for valid
values. Automatic calibration during compressor startup failed.
Axial Displacement Fault
Axial Orbit has exceeded the limit longer than the maximum time
allowable.
Axial Overcurrent Fault
Axial Current has exceeded the limit longer than the maximum time
allowable.
Front Radial Displacement Fault
Front Radial Orbit has exceeded the limit longer than the maximum time
allowable.
Front Radial X Overcurrent Fault
Front Radial X Current has exceeded the limit longer than the maximum
time allowable.
Front Radial Y Overcurrent Fault
Front Radial Y Current has exceeded the limit longer than the maximum
time allowable.
Rear Radial Displacement Fault
Rear Radial Orbit has exceeded the limit longer than the maximum time
allowable.
Rear Radial X Overcurrent Fault
Rear Radial X Current has exceeded the limit longer than the maximum
time allowable.
Rear Radial Y Overcurrent Fault
Rear Radial Y Current has exceeded the limit longer than the maximum
time allowable.
Summary of Contents for Turbocor TTS Series
Page 14: ...14 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...30 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 38: ...38 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...40 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...46 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...50 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 238: ...238 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 240: ...240 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 260: ...260 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 262: ...262 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...268 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 276: ...276 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 280: ...280 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...