272 of 282
M-SV-001-EN Rev. G
Figure B-21 Compressor Operation Troubleshooting Flowchart (Sheet 2)
E
H
F
G
B
C
Refer to Section 4.5
“Voltage
Troubleshooting”
Are I/O cable and
BMCC board securely
connected?
Yes
No
No
Is DC Bus voltage is
within spec
No
Disconnect power,
secure
component(s)
Refer to Section
4.26.2 “BMCC
Verification”
Yes
No
A
Close interlock
circuit
Is
there a demand %
displayed?
Yes
No
Restore demand
input to the
compressor
Has
the IGV reset?
No
Yes
Wait until IGV reset
Is Inverter Temp
below Maximum Start
Temp?
No
Yes
Refer to Section
5.5.4
“Troubleshooting
the Inverter”
Have all Start Delay
Timers have expired?
No
Yes
A
Yes
Wait until all Start
Delay Timers have
expired
No
End
Refer to Section 5.0
“Troubleshooting”
Yes
No
Can
fault be reset by
cycling the power?
No
Yes
End
Refer to Section
4.14.2 “Soft Start
Verification”
Refer to Section
4.23.2 “DC‐DC
Verification”
Yes
A
A
D
Note the IGV settings
Summary of Contents for Turbocor TTS Series
Page 14: ...14 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...30 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 38: ...38 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...40 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...46 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...50 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 238: ...238 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 240: ...240 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 260: ...260 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 262: ...262 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...268 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 276: ...276 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 280: ...280 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...