7. Continue to "4.19.2.10 SCR Temperature Sensor Installation - TTS/TGS/TTH/TGH Rev. F and
Earlier (Except TTS300/TGS230)".
Figure 4-155 SCR Temperature Sensor Removal - TTS/TGS/TTH/TGH Rev. F and Earlier (Except TTS300/TGS230)
4.19.2.9 SCR Temperature Sensor Installation - TTS300/TGS230
1. Carefully thread the SCR Temperature Sensor into the SCR Cooling Manifold and torque to 6
Nm (53 in.lbs.).
2. Connect the SCR Temperature Sensor to the Compressor controller Harness and carefully slide
the sensor cable under the SCR Cooling Manifold from the discharge side of the compressor.
Refer to "Figure 4-151 SCR Temperature Sensor Connector - TTS300/TGS230" on page 138.
3. Install the Terminal Block. Refer to "4.12.2.2 Specific 3-Phase Main Voltage Input Terminal Block
Removal - TTS300/TGS230" on page 98.
4. Connect the discharge pressure/temperature sensor connector if it was removed.
5. Continue to "4.19.2.11 SCR Temperature Sensor General Installation".
4.19.2.10 SCR Temperature Sensor Installation - TTS/TGS/TTH/TGH Rev. F and Earlier (Except TTS300/TGS230)
1. Carefully thread the SCR Temperature Sensor into the SCR Cooling Manifold and torque to 6
Nm (53 in.lbs.).
2. Connect the discharge pressure/temperature sensor connector if it was removed.
3. Install the SCR Temperature Sensor Cable in the same location. It should be on top of the SCR
Cooling Manifold and next to the Inverter. Refer to "Figure 4-153 SCR Temperature Sensor
Connector - TTS/TGS/TTH/TGH Rev. F and Earlier (Except TTS300/TGS230)" on page 139.
4. Install the Capacitor and DC Bus Assembly and verify the SCR Temperature Sensor Cable is
not pinched. Refer to "4.22.4.4 DC Capacitor Bus Bar Assembly Installation - TTS/TGS/TTH/TGH
(Except TTS300/TGS230)" on page 163.
5. Install the Terminal Block and AC Bus Bars. Refer to "4.12 3-Phase Main Voltage Input Terminal
6. Connect the Soft Start AC wires to the AC Bus Bars.
7. Continue to "4.19.2.11 SCR Temperature Sensor General Installation".
4.19.2.11 SCR Temperature Sensor General Installation
1. Install the Soft Start. Refer to "4.15 Soft Start" on page 107.
2. Install the top covers. Refer to "4.2 Compressor Covers" on page 56.
3. Return the compressor to normal operation.
SCR Temperature
Sensor
• • • CAUTION • • •
Be careful to not damage the wire exiting the SCR Temperature Sensor when tightening.
• • • CAUTION • • •
Be careful to not damage the wire exiting the SCR Temperature Sensor when tightening.
Summary of Contents for Turbocor TTS Series
Page 14: ...14 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...30 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 38: ...38 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...40 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 46: ...46 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...50 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 238: ...238 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 240: ...240 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 260: ...260 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 262: ...262 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...268 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 276: ...276 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...
Page 280: ...280 of 282 M SV 001 EN Rev G THIS PAGE INTENTIONALLY LEFT BLANK...