34 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
3.2.2.3 Calibration
1. Connect to the Compressor with the SMT.
2. Open the
Valve Control Setup Tool.
3. Under the IFV tab, click on
Calibrate IFV.
NOTE
IFV calibration may take up to several minutes.
4. A pop-up window in the SMT should state that the IFV calibrated successfully.
10. Press the
Up Arrow
button until you reach Parameter 26.
11. Press the
Enter/Edit
button.
12. Press the
Up Arrow
button to select 5.
13. Press the
Enter/Edit
button.
14. Hold the
Enter/Edit
button for 2 seconds to exit the programming mode.
3.2.3 ICM Body
The ICM attaches to the IFV Pipe Assembly. The driving force from the IFV is transferred via a magnetic
coupling through the stainless steel valve stem on the Bonnet/Function Module. This action permits
the regulation of the refrigerant flow to the inlet of the first stage diffuser.
ICM Body Bolts - 100
Nm (74 ft.lb.) (4 places)
ICM Adapter/Valve
Stem
Bonnet/Function
Module
Figure 21 - ICM Body
3.2.2.4 Torque
Specifications
Description
Nm
Ft.Lb.
In.Lb.
IFV Set Screws
3
-
27
Table 7 - IFV Actuator Torque
Specifications
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...