Variable Frequency Drive Components
Installation:
1. Route the cable into the DC-DC box.
2. Connect to (J1) HV IN on the DC-DC Board.
3. Connect the HV DC Ground cable to the DC-DC Board.
4. Secure the cable where it goes into the box.
5. Route the cable into the bottom of the VFD.
6. Connect to + Regen 82 and – Regen 83.
7. Secure the cable where it goes into the power module.
8. Replace all covers.
9. Reconnect power to the VFD.
Description
Nm
Ft.Lb.
In.Lb.
+ and - Regen Screws, M5
19
14
168
Table 34 - Regen Cable
Torque Specifications
4.6.2 VFD DC-DC Cable
Verification
1. Apply power to the VTT VFD.
2. Verify the LEDs on CIM are on.
3. On the DC-DC, using an appropriately rated voltage meter, verify HV DC input is correct for the
applied voltage by checking at VDC+ (J12) and VDC- (J13) test points.
4. The measured voltage should be around 1.35 x the AC input voltage.
5. Verify 24 V DC output is correct by checking at J10 and J11 test points.
6. Verify 250 V DC output is correct by checking at J8 and J9 test points.
4.6.3 Torque
Specifications
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...