56 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
3.3.3.1 Removal and
Installation
Motor Terminal Block Removal:
1. Isolate the Compressor power as described in the
“Electrical Isolation of the Compressor/VFD”
section of this manual.
2. Remove the Motor Power Cover.
3. Remove the three (3) M10 nuts, flat washers, and lock washers off the top of the copper spacers.
4. Remove the six (6) motor power cables (two (2) cables per phase). Protect/isolate the cable ends.
5. Remove the three (3) copper spacers.
6. Remove the three (3) M16 brass nuts, lock washers, and flat washers from the Motor Tower Feed
Through.
7. Remove the four (4) M5 screws, lock washers, and flat washers that attach the terminal block to
the Compressor.
8. Remove the six (6) M5 screws, lock washers, and flat washers that attach the bus bar to the
Motor Terminal Block.
9. Remove the Motor Terminal Block from the Compressor.
Motor Terminal Block Installation:
1. Place the Motor Terminal Block on the Compressor by aligning the bus bars onto the Motor
Tower Feed Throughs.
2. Secure the terminal block to the Compressor with the four (4) M5 screws and washers and
torque to specification.
3. Install the three (3) M16 brass nuts, flat washers, and lock washers from the Motor Tower Feed
Through.
4. Install the three (3) copper bus bars onto the studs on the terminal block.
5. Install the three (3) copper spacers.
6. Connect the six (6) motor power cables (two (2) cables per phase).
7. Install the three (3) M10 nuts, flat washers, and lock washers on the studs above the copper
spacers and power cables and torque to specification.
8. Restore power to the Compressor.
3.3.3.2 Verification
• • • DANGER • • •
• This equipment contains hazardous voltages that can cause injury or death. Exercise extreme
caution when working on energized circuits.
• Always wear safety glasses when working around components energized by high voltages.
Faulty components can explode and cause serious eye injuries.
Connecting the AC Input Cables:
1. Isolate the Compressor power as described in the
“Electrical Isolation of the Compressor/VFD”
section of this manual.
2. Ensure the AC cables are securely fastened to the Motor Terminal Block.
3. If the cables cannot be securely fastened to the input terminal, the Motor Terminal Block is
damaged and needs to be replaced.
Verifying the 3-Phase AC Input:
1. Turn ON the AC input power.
2. Set the multimeter for AC voltage measurements.
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...