59 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Figure 53 - Tower Plate
Torque Pattern
8. Leak test the Compressor to the appropriate pressure and industry standards.
9. Evacuate the Compressor to the appropriate pressure and industry accepted standards.
10. Charge the Compressor with refrigerant.
11. Restore power to the Compressor
1
2
3
8
10
5
7
9
4
6
Description
Nm
Ft.Lb.
In.Lb.
Tower Plate, SHCS, M6x30
10
7
89
Table 18 - Tower Plate
Torque Specifications
3.3.4.2 Torque
Specifications
3.3.5 Motor Power Feed
Through
The Motor Power Feed Through connects the Motor Bus Bars to the internal motor leads while
preventing refrigerant pressure from escaping.
Figure 54 - Motor Power
Feed Through
• • • CAUTION • • •
Disassembling the Motor Power Feed Through poses a risk that can lead to permanent damage.
All hardware and tools
must
be accounted for prior to restarting the Compressor.