83 of 165
M-SV-VT-001-EN Rev. A
Compressor Components
Installation:
1. Route cable between the CCM and CIM.
2. Connect cable to J2 CCM/CAN termination on the CIM.
3. Connect opposite end of cable to J17 CIM on CCM Board.
4. Secure cables in location.
5. Reinstall the covers.
6. Restore power to the Compressor and verify proper operation.
3.7.1.5.2 CCM-CIM Cable
Verification
1. With Power applied to the Compressor, connect to the CIM using the SMT and enter the User ID
and Access Code.
2. Open the Warnings and Faults Tool.
3. Verify that the CIM Compatibility, CAN Communications and VFD Communications Faults are
not active.
3.7.1.6 CCM-VFD Cable
The VFD Cable provides a connection for communication between the CCM and the VFD.
Figure 90 - CCM-VFD Cable
(Revisions A and B)
Figure 91 - CCM-VFD Cable
(Revisions C and Later)
3.7.1.6.1 Removal and
Installation
Removal:
1. Isolate the Compressor and VFD power as described in the
section of this manual.
2. Remove the Compressor Service Side Cover.
Figure 92 - J4 Connector
(Revisions A and B)
J4 Connector
Summary of Contents for Turbocor VTT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...12 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...18 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...24 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 132: ...132 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 152: ...152 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 158: ...158 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 160: ...160 of 165 M SV VT 001 EN Rev A THIS PAGE INTENTIONALLY LEFT BLANK ...