*) You can isolate digital inputs from ground with a DIP switch. See
7.3.2 Isolation of the Digital Inputs from Ground
There are 2 different relay boards available. If you include the optional code +SBF4 in your order, the relay output 3 is replaced with a
thermistor input.
The thermistor input function is not automatically active. To use the thermistor input function, activate the parameter Thermistor Fault
in the software. See the Application Guide.
RO1 NC
RO1 CM
RO1 NO
RO2 NC
RO2 CM
RO2 NO
RO3 CM
RO3 NO
21
22
23
24
25
26
32
33
e3
0b
h3
29
.1
0
RUN
RUN
FAULT
READY
Relay output 1
Relay output 2
Relay output 3
From Standard I/O board
Terminal
Signal
Default
Relay board 1
From term. #6
or 12
From term.
#13
Illustration 21: Standard Relay Board (+SBF3)
RO1 NC
RO1 CM
RO1 NO
RO2 NC
RO2 CM
RO2 NO
TI1+
TI1-
21
22
23
24
25
26
28
29
e3
0b
h3
30
.1
0
RUN
RUN
FAULT
NO ACTION
Relay output 1
Relay output 2
From Standard I/O board
Terminal
Signal
Default
Relay board 2
From term.
#12
From term.
#13
Thermistor input
Illustration 22: Optional Relay Board (+SBF4)
7.3 DIP Switches on the Control Unit
7.3.1 Selection of Terminal Functions with DIP Switches
Two selections for specified terminals can be done with the DIP switches. The switches have two positions: up and down. See the
location of the DIP switches and the possible selections in
Control Unit
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 67