The option board
The name of the option board
The correct slot or slots
OPTE3
The PROFIBUS DPV1 fieldbus board
D, E
OPTE5
The PROFIBUS DPV1 fieldbus board (with a type D connector)
D, E
OPTE6
The CANopen fieldbus board
D, E
OPTE7
The DeviceNet fieldbus board
D, E
OPTE8
The RS485 (Modbus/N2) fieldbus board (with a type D connector)
D, E
OPTE9
The Dual-port ethernet fieldbus board
D, E
OPTEA
The Advanced dual-port ethernet fieldbus board
D, E
OPTEC
The EtherCAT fieldbus board
D, E
7.6 Option Board Installation
Prerequisites:
WARNING
SHOCK HAZARD FROM CONTROL TERMINALS
The control terminals can have a dangerous voltage also when the drive is disconnected from mains. A contact with this
voltage can lead to injury.
-
Make sure that there is no voltage in the control terminals before touching the control terminals.
CAUTION
DAMAGE TO OPTION BOARDS
Do not install, remove, or replace option boards on the drive when the power is on. Doing this can cause damage to the boards.
-
Switch off the AC drive before installing, removing, or replacing option boards on the drive.
NOTICE
INCOMPATIBLE OPTION BOARDS
It is not possible to install option boards that are not compatible with the drive.
If the installed board is an OPTB or an OPTC option board, make sure that the label on it says "dv" (dual voltage). This marking shows
that the option board is compatible with the drive.
Control Unit
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 85
Danfoss A/S © 2019.05