Description of parameters
vacon · 63
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
5
if 100% of Base Current Reference is given, the drive will feed 100% power to the grid.
The situation is the same with the frequency reference set to 52 Hz and with 2.000 Hz
drooping.
Base current reference can be used together with selection
3
of P2.11.5
StartPowerMode: Isochron.Gen. This selection will keep the drive frequency reference
same as the grid frequency, and the power that is fed or taken from the drive is solely
defined by the Base Current Reference parameter.
+1
%
+2%
+3%
+4%
-1%
-2%
-3%
-4%
50,5 Hz
51,0 Hz
51,5 Hz
52,0 Hz
48,0 Hz
48,5 Hz
49,0 Hz
49,5 Hz
50,0 Hz
L
oad
ing
U
n
-l
o
adi
ng
Droo
ping
Freq.
Change
25%
50%
75%
100%
Related
Load
Figure 15.
2.2.4.7
Base Reference Ramp Rate
ID1536
This parameter defines the increase rate of the base current reference when the
reference is changed or the drive is started.
Input Ref.
Current
Reference
110 %
10 %
Internal Ref
50 % / s
2 s
Figure 16.
2.2.4.8
Base Reference to Zero
ID1537
This parameter defines in which situations Base Current Reference is set to the value of
P2.2.6.8 BaseRefAtStop.