12.7.6 Power Ratings for Mains Voltage 525–690 V (UL Rating 600 V)
Table 55: Power Ratings in Mains 525–600 V, 50 Hz, 3~
Enclosure
size
Drive
type
Input
current
I
in
(1)
Low
loadabil‐
ity: I
L
[A]
(2)
Low
loadabil‐
ity: 10%
overload
I [A]
High
loadabil‐
ity: I
H
[A]
(2)
High
loadabil‐
ity: 50%
overload
I [A]
Loadabili‐
ty: Max I
S
2 s
Motor
shaft
power
(3)
:
10%
overload
40°C [kW]
Motor
shaft
power
(3)
:
50%
overload
50°C [kW]
FR6
0004
4.5
4.5
5.0
3.2
4.8
6.4
3.0
2.2
0005
5.5
5.5
6.1
4.5
6.8
9.0
4.0
3.0
0007
7.5
7.5
8.3
5.5
8.3
11.0
5.5
4.0
0010
10.0
10.0
11.0
7.5
11.3
15.0
7.5
5.5
0013
13.5
13.5
14.9
10.0
15.0
20.0
11.0
7.5
0018
18.0
18
19.8
13.5
20.3
27.0
15.0
11.0
0022
22.0
22.0
24.2
18.0
27.0
36.0
18.5
15.0
0027
27.0
27.0
29.7
22.0
33.0
44.0
22.0
18.5
0034
34.0
34.0
37.0
27.0
41.0
54.0
30.0
22.0
FR7
0041
41.0
41.0
45.0
34.0
51.0
68.0
37.5
30.0
0052
52.0
52.0
57.0
41.0
62.0
82.0
45.0
37.5
FR8
0062
62.0
62.0
68.0
52.0
78.0
104.0
55.0
45.0
0080
80.0
80.0
88.0
62.0
93.0
124.0
75.0
55.0
0100
100.0
100.0
110.0
80.0
120.0
160.0
90.0
75.0
FR9
0125
125.0
125.0
138.0
100.0
150.0
200.0
110.0
90.0
0144
144.0
144.0
158.0
125.0
188.0
250.0
132.0
110.0
0170
170.0
170.0
187.0
144.0
216.0
288.0
160.0
132.0
0208
208.0
208.0
229.0
170.0
255.0
340.0
200.0
160.0
FR10
(3)
0261
261.0
261.0
287.0
208.0
312.0
416.0
250.0
200.0
0325
325.0
325.0
358.0
261.0
392.0
522.0
315.0
250.0
0385
385.0
385.0
424.0
325.0
488.0
650.0
355.0
315.0
0416
416.0
416.0
358.0
325.0
488.0
650.0
400.0
315.0
FR11
(3)
0460
460.0
460.0
506.0
385.0
578.0
770.0
450.0
355.0
0502
502.0
502.0
552.0
460.0
690.0
920.0
500.0
450.0
0590
590.0
590.0
649.0
502.0
753.0
1004.0
560.0
500.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See
3
690 V
Specifications
Operating Guide | VACON® NXS/NXP Air-cooled
AQ275638903263en-000301 / DPD00910| 187