12.10.102 Fault 42 - Brake resistor overtemperature, Subcode S4 - Brake resistance not detected
(BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
12.10.103 Fault 42 - Brake resistor overtemperature, Subcode S5 - Brake resistance leakage (earth
fault) (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
12.10.104 Fault 43 - Encoder fault, Subcode S1 - Encoder 1 channel A is missing
Cause
Problem detected in encoder signals.
Encoder channel A is missing.
Troubleshooting
•
Do a check of the encoder connections.
•
Do a check of the option board.
•
Measure the encoder pulses.
-
If the pulses are correct, the option board is faulty.
-
If the pulses are not correct, the encoder/cabling is faulty.
12.10.105 Fault 43 - Encoder fault, Subcode S2 - Encoder 1 channel B is missing
Cause
Problem detected in encoder signals.
Encoder channel B is missing.