When using parallel cables, make sure to obey the requirements of the cross-sectional area and the maximum number of cables.
For important information on the requirements of the grounding conductor, see the NEC and CEC.
For the correction factors for each temperature, see the instructions of NEC and CEC.
6.1.5 Fuse Selection
We recommend the fuse type gG/gL (IEC 60269-1). To make a selection of the fuse voltage rating, refer to the mains. Refer also to local
regulations, cable installation conditions, and cable specification. Do not use larger fuses than what is recommended.
External fuses in the input line are required for overload and short-circuit protection of the drive.
Find the recommended fuses in tables in
12.3.1 List of Cable and Fuse Size Information
Make sure that the operation time of the fuse is less than 0.4 s. The operation time agrees with the fuse type and the impedance of the
supply circuit. For more information on faster fuses, speak to the manufacturer. The manufacturer can also recommend some aR (UL
recognized, IEC 60269-4) and gS (IEC 60269-4) fuse ranges.
6.1.6 Principle of the Power Unit Topology
.
A
B
B
C
FR4-9/FR10/
FR11 0460 6 & 0502 6
FR11 *)
e
3
0
b
g
0
8
0
.1
0
A Single input
C Double input
B Single output
* The FR11 types 0460 6 and 0502 6 have single input terminal.
Illustration 15: Topology of Enclosure Sizes FR4 – FR11
6.1.7 Brake Resistor Cables
VACON
®
NXS/NXP AC drives have terminals for the DC supply and an optional external brake resistor. These terminals are identified
with B–, B+/R+, and R–. The DC bus connection is made to terminals B– and B+ and the brake resistor connection to R+ and R–. Danfoss
recommends shielded motor cable to be used for the brake resistor. Only two conductors of a normal three phase cable are needed.
The shield of the cable must be connected at each end. 360 ° grounding of the shield is recommended to minimize interference. The
third, unused connector must be grounded by connecting it to ground at one end.
See list of recommended cables in
12.3.1 List of Cable and Fuse Size Information
.
Electrical Installation
Operating Guide | VACON® NXS/NXP Air-cooled
AQ275638903263en-000301 / DPD00910| 43