Example 2 with full speed range from 30rps (1800rpm) to 140rps (8400rpm)
Safeties required
High-pressure switch, Low pressure switch, Discharge gas thermostat set @135°C (275°F) if
necessary see Discharge temperature protection.
Drive setting
No parameter change required, keep default value
Envelope control
The unit controller continuously measures evaporating and condensing temperatures, as well as
maintains compressor speeds according to
specific
zone restrictions.
C
ondensing t
emper
atur
e (°C
)
Evaporating temperature (°C)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
30-140rps
30-120rps
C
ondensing t
emper
atur
e (°F)
41
50
59
68
77
86
95
104
113
122
131
140
149
158
Danfoss
OE-000001
Evaporating temperature (°F)
-40
-31
-22
-13
-4
5
14
23
32
41
50
59
68
77
86
Manage sound and vibration
Sound level
The sound radiating from the compressor is emitted through the air, the sound waves travel in all directions from
the compressor.
Scroll compressors, VCH115 | Application
© Danfoss | Climate Solutions | 2023.08
AB392939083370en-000202 | 36