VFD500 high performance vector control frequency inverter user manual Chapter 5 function code table
P23.18
Fault protection action
selection 1
Unit’s digit : input phase loss
0: coast to stop
1: Emergent stop
2: Stop as per stop mode
3: Continue to Run
Ten’unit: user self-defined fault 1
same as Unit’s digit
Hundred’unit: user self-defined fault 2
same as Unit’digit
Thousand’s unit: communication fault
same as unit’s digit
0000
☆
P23.19
Fault protection action
selection 2
Unit’s digit: motor overload
0: Coast to stop
1: Emergent stop
2: Stop as per stop mode
3: Continue to run
Ten’unit: motor overheat
same as unit’digit
Hundred’unit: too large speed deviation
same as unit’digit
Thousand’s unit: motor over speed
same as Unit’digit
0000
☆
P23.20
Fault protection action
selection 3
Unit’s digit: PID feedback lost during running
0: Coast to stop
1: Fast stop
2: Stop as per stop mode
3: Continue to run
Ten’unit: Reserved
same as unit’digit
Hundred’unit: reserved
same as unit’digit
thousand’unit: reserved
same as unit’digit
0000
☆
P23.21
Fault protection action
selection 4
Unit’s digit: output phase loss
0: Coast to stop
1: Fast stop
2: Stop as per stop mode
Ten’unit: EEPROM fault
0: Coast to stop
1: Fast stop
2: Stop as per stop mode
3: Continue to run
Hundred’s unit: PG card fault(reserved)
0: Coast to stop
1: Fast stop
2: Stop as per stop mode
3: Continue to run
Thousand’s unit: off load fault
0: Coast to stop
1: Fast stop
2: Stop as per stop mode
3: Continue to run
0000
☆
P23.24
Fault reset
Define as per bit:
bit0-undervoltage;bit1- inverter overload
bit2-inverter overheat ;bit3-motor overload
bit4-motor overheat;bit5-user’fault 1
bit6- user’fault 2; bit7
~
15 reserved
0
☆
87