Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
P23.25
Fault source for auto reset
Define as per bit:
bit0-overcurrent during acceleration;bit1-
overcurrent during deceleration
bit2-overcurrent during constant speed;bit3-over
voltage during acceleration
bit4-overvoltage during deceleratoin;bit5-
overvoltage during
bit6-inverter undervoltage;bit7-input phase loss
bit8-inverter overload;bit9-inverter overheat
bit10-motor overload;bit11-motor overheat
bit12-user’fault 1;bit13-user’fault 2
bit14-Reserved;bit15-Reserved
0
☆
P23.26
Fault auto Reset times
0
~
99
0
☆
P23.27
Numberic output Action at
fault reset
0:Disabled
1:Enabled
0
☆
P23.28
Interval time of fault auto
reset
0.1s
~
300.0s
0.5s
☆
P23.29
Fault auto reset times
clearing time
0.1s
~
3600.0s
10.0s
☆
P23.30
Continuing Running
frequency selection when
trip
0
:
Run at current frequency
1
:
Run at setted frequency
2
:
Run at upper limite frequency
3
:
Run at lower limit frequency
4
:
Run at abnormal back-up frequency
0
☆
P23.31
Abnormal back-up
frequency
0.0%
~
100.0%(maximum frequency )
5.0%
☆
24 Group motor Protection parameter
P24.00
Motor overload protection
gain
0.20
~
10.00
The larger the value, the longer the allowable
overload operation, and the higher the risk of
motor overheating damage.
1.00
☆
P24.01
Motor overload starting
current at zero speed
50.0%
~
150.0%
100.0%
☆
P24.02
Motor overload starting
current at Rated speed
50.0%
~
150.0%
115.0%
☆
88