Interpreting 

 

1 Flash

There is insufficient voltage reaching the fridge compressor.  

  

PENGUIN REFRIGERATION LTD

Unit  2b 

 

Alexandria  Park 

T:  02392  453293

www.penguinfrigo.co.uk

Page  1 

Registered in England

The Danfoss BD35 and BD50 compressors have their own fault diagnostic allowing 
easy fault finding.
start or stops.

Start by Linking out the Thermostat

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

Connect the LED faul

If an LED light is 
control  box
compressor refuses to start.

 

Hint:

An  electrical  multi  meter  can  be 
continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 
a signal.

Interpreting 

1 Flash

 

There is insufficient voltage reaching the fridge compressor.  

PENGUIN REFRIGERATION LTD

Alexandria  Park 

 

Penner 

02392  453293

  

F:  02392  453293

www.penguinfrigo.co.uk

 

Registered in England

 

No: 4310267                                                                                                                  

Danfoss BD 35 and 50F Fault Diagnostic.

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

easy fault finding.

  

start or stops.

 

Start by Linking out the Thermostat

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

Connect the LED faul

light is connected between the 

control  box,  as  shown  in  the  diagram  above
compressor refuses to start.

Hint:

  

An  electrical  multi  meter  can  be 
continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 
a signal.

 

Interpreting the results

 

Low Voltage

There is insufficient voltage reaching the fridge compressor.  

PENGUIN REFRIGERATION LTD

Penner  Road 

 

Havant 

02392 453293

  

E: sales@penguinfrigo.co.uk

No: 4310267                                                                                                                  

Danfoss BD 35 and 50F Fault Diagnostic.

 

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

  

The fault code will only be shown when 

Start by Linking out the Thermostat

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

Connect the LED fault diagnosis curcuit

connected between the 

as  shown  in  the  diagram  above

compressor refuses to start.  

An  electrical  multi  meter  can  be 
continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

results

 

Low Voltage

 

There is insufficient voltage reaching the fridge compressor.  

PENGUIN REFRIGERATION LTD

 

Havant 

 

Hants 

E:  sales@penguinfrigo.co.uk

No: 4310267                                                                                                                  

Danfoss BD 35 and 50F Fault Diagnostic.

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

The fault code will only be shown when 

Start by Linking out the Thermostat

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

t diagnosis curcuit

connected between the 

as  shown  in  the  diagram  above

  

 

An  electrical  multi  meter  can  be 
continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

 

There is insufficient voltage reaching the fridge compressor.  

Hants 

 

PO9  1QY

 

E:  sales@penguinfrigo.co.uk

 

Suppliers of

   

  

No: 4310267                                                                                                                  

 

Danfoss BD 35 and 50F Fault Diagnostic.

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

The fault code will only be shown when 

Start by Linking out the Thermostat

 

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

t diagnosis curcuit

 

connected between the small positive 

as  shown  in  the  diagram  above

An  electrical  multi  meter  can  be  used  instead  of  an  LED.  Set  the  meter  to 
continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

There is insufficient voltage reaching the fridge compressor.  

 

Suppliers of

 

No: 4310267                                                                                                                  

Danfoss BD 35 and 50F Fault Diagnostic.

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

The fault code will only be shown when 

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

small positive 

as  shown  in  the  diagram  above,  it  will  flash  an  error  code  if  the 

used  instead  of  an  LED.  Set  the  meter  to 

continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

There is insufficient voltage reaching the fridge compressor.  

No: 4310267                                                                                                                                 

Danfoss BD 35 and 50F Fault Diagnostic.

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

The fault code will only be shown when the compressor fails to 

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

small positive (+) and 

it  will  flash  an  error  code  if  the 

used  instead  of  an  LED.  Set  the  meter  to 

continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

There is insufficient voltage reaching the fridge compressor.  

 

               VAT No: GB 785 5650 85

Danfoss BD 35 and 50F Fault Diagnostic.

 

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

the compressor fails to 

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

and  D

 

terminal 

it  will  flash  an  error  code  if  the 

used  instead  of  an  LED.  Set  the  meter  to 

continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

VAT No: GB 785 5650 85

 

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

the compressor fails to 

To ensure the thermostat is not causing problems put a link out between C and T 
terminals this will force the compressor to run continually during testing.

 

terminal on the 

it  will  flash  an  error  code  if  the 

used  instead  of  an  LED.  Set  the  meter  to 

continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

VAT No: GB 785 5650 85

 

anfoss BD35 and BD50 compressors have their own fault diagnostic allowing 

the compressor fails to 

To ensure the thermostat is not causing problems put a link out between C and T 

the 

it  will  flash  an  error  code  if  the 

used  instead  of  an  LED.  Set  the  meter  to 

continuity  (will  also  have  a  beep  alarm  when  continuity  is  made).  Put  the 
probes on the small + and the D terminal and the meter will sound or show 

Reviews: