464
Wakeup Pressure
(Wakeup Pressure)
Value:
Par. 204 Ref
MIN
– par. 215 - 218 Setpoint
0
Function:
When in Sleep mode the frequency converter will wake
up when the pressure is below the Wakeup pressure
for the time set in parameter 462
Enhanced sleep mode
timer
.
Description of choice:
Set an appropriate value for the system. The unit is set
in parameter 416.
465
Minimum pump frequency
(Pump min. freq.)
Value:
Value par. 201 f
MIN
– par. 202 f
MAX
(Hz)
20
Function:
This parameter is linked to parameter 467
Minimum
Power
and is used for no/low flow power curve.
Description of choice:
Enter a value equal or close to the desired minimum
frequency set in parameter 201
Output frequency low
limit, f
MIN
. Please note, that the extension of the no/low
flow power curve is limited by parameters 201 and 202
and not by parameters 465 and 466.
466
Maximum Pump Frequency
(Pump max. freq)
Value:
Value par. 201 f
MIN
- par. 202 f
MAX
(Hz)
50
Function:
This parameter is linked to parameter 468
Maximum
pump power
and is used for the no/low flow power
curve.
Description of choice:
Enter a value equal or close to the desired maximum
frequency set in parameter 202
Output frequency high
limit, f
MAX
.
467
Minimum Pump Power
(Min. pump power)
Value:
0 – 500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 465
Minimum pump frequency
.
Description of choice:
Enter the no/low flow power reading at minimum pump
frequency entered in parameter 465.
Depending on pump size or curve select W or kW in
par. 009 index [32] and [8] for fine tuning.
468
Maximum Pump Power
(Max. pump power)
Value:
0 – 500.000 W
0
Function:
The associated power consumption at the frequency
entered in parameter 466
Minimum pump frequency
.
Description of choice:
Enter the no/low flow power reading at maximum
pump frequency entered in parameter 466.
Depending on pump size or curve select W or kW in
par. 009 index [32] and [8] for fine tuning.
469
No Flow Power Compensation
(NF power comp)
Value:
0.01 - 2
1.2
Function:
This function is used for an off-set of the no/low flow
power curve, which can be used as a safety factor or
for fine tuning of the system.
Description of choice:
Description The factor is multiplied to the power val-
ues. E.g. 1.2 will increase the power value with 1.2
over the whole frequency range.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.27.A2.02 - VLT
®
is a registered Danfoss trademark
55
Programming
Summary of Contents for VLT 2800 Series
Page 1: ...VLT 2800 MG27A202 VLT 2800 Operating Instructions Operating Instructions...
Page 62: ...192H4893 VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 61 Installation...
Page 76: ...VLT 2800 Series MG 27 A2 02 VLT is a registered Danfoss trademark 75 All about VLT 2800...
Page 77: ...VLT 2800 Series 76 MG 27 A2 02 VLT is a registered Danfoss trademark...
Page 103: ......