15
INTERFACE BOARD LED'S
OC (D8-YELLOW)
OCT (D7-RED)
IOK (D4-GREEN)
LBV (D6-RED)
HBV (D5-RED)
GFT (D2-RED)
OTT (D3-RED)
PSF (D1-RED)
LOP (D9-RED)
IOT (D109-YELLOW)
EOT (D108-YELLOW)
HIGH BUS VOLTAGE
HBV (D5-RED)
Indicates the DC Bus voltage upper limit has been
exceeded.
The I0K LED will be off and the control card indicates
"Over Voltage".
LOW BUS VOLTAGE
LBV (D6-RED)
Indicates the DC Bus voltage has fallen below the lower
limit.
The I0K LED will be off and the control card will indicate
"Under Voltage".
OVER CURRENT TRIP
OCT (D7-RED)
Indicates a short circuit on the inverter output.
The I0K LED will be off and the control card will indicate
"Over Current".
GROUND FAULT TRIP
GFT (D2-RED)
Indicates a Ground Fault on the Inverter Output.
The I0K LED will be off and the control card will indicate
"Ground Fault".
OVER TEMP TRIP
OTT (D3-RED)
Indicates the heatsink temperature is outside of the specified operating
range.
The I0K LED will be off and the control card will indicate "Over Temp".
INTERNAL OVER TEMP
IOT (D109-YELLOW)
Indicates the internal ambient temperature has been exceeded.
The I0K LED will be off and the control card will indicate "Over Temp".
ALARM MESSAGES
(continued)
CURRENT LIMIT (9)
This message will be displayed if the unit has run in current limit for a
time which exceeds the setting in parameter 310. To remedy this fault,
reduce the motor's load or verify that the correct settings have been
entered in parameter 209 (Current Limit) and parameter 310 (Current
Limit Trip Delay). This fault returns a "Trip". See Current Limit Trips,
page 35.
INTERFACE BOARD LED'S