VLT
®
4000 VT
Installation
■
Line supply 3 x 380 - 460 V
According to international requirements
VLT type
4006
4008
4011
Output current
I
VLT,N
[A] (380-440 V)
10.0
13.0
16.0
I
VLT, MAX
(60 s) [A] (380-440 V)
11.0
14.3
17.6
I
VLT,N
[A] (441-460 V)
8.2
11.0
14.0
I
VLT, MAX
(60 s) [A] (441-460 V)
9.0
12.1
15.4
Output
S
VLT,N
[kVA] (400 V)
7.2
9.3
11.5
S
VLT,N
[kVA] (460 V)
6.5
8.8
11.2
Typical shaft output
P
VLT,N
[kW]
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
5
7.5
10
Max. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2
)
4/10
4/10
4/10
Max. input current
I
L,N
[A] (380 V)
9.1
12.2
15.0
(RMS)
I
L,N
[A] (460 V)
8.3
10.6
14.0
Max. cable cross-section,
power
[mm
2
]/[AWG]
2
)
4/10
4/10
4/10
Max. line-fuses
1)
[A]/UL [A]
25/20
25/20
35/30
Efficiency
3)
0.96
Weight NEMA 1
[lbs]
21
21
21
Weight NEMA 12
[lbs]
28
28
28
Power loss at max. load. [W]
Total
198
250
295
Enclosure
VLT type
Compact NEMA 1/NEMA 12
1 See section
Fuses.
2 American Wire Gauge.
3 Measured using 100 feet shielded motor cable at rated load and rated frequency.
4 Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on
min. cable cross-section.
MG.40.A7.22 - VLT is a registered Danfoss trademark