VLT
®
4000 VT
Programming
■
Relay outputs
Relay outputs Relay outputs 1 and 2 can be used to give the present status or a warning.
Relay 1
1 - 3 break, 1 - 2 make
Max. 240 V AC, 2 Amp.
The relay is placed with the
line and motor terminals.
Relay 2
4 - 5 make
Max. 50 V AC, 1 A, 60 VA.
Max. 75 V DC, 1 A 30 W.
The relay is placed on the control card, see
Electrical installation, control cables.
Relay Outputs
terminal no.
1
2
parameter
323
326
Value:
No function (NO FUNCTION)
[0]
[0]
Ready signal (READY)
[1]
[1]
Standby (STAND BY)
[2]
[2]
Running (RUNNING)
[3]
✭
[3]
Running at ref. value (RUNNING AT REFERENCE)
[4]
[4]
Running, no warning (RUNNING NO WARNING)
[5]
[5]
Local reference active (DRIVE IN LOCAL REF)
[6]
[6]
Remote references active (DRIVE IN REMOTE REF.)
[7]
[7]
Alarm (ALARM)
[8]
[8]
Alarm or warning (ALARM OR WARNING)
[9]
[9]
No alarm (NO ALARM)
✭
[10]
[10]
Current limit (CURRENT LIMIT)
[11]
[11]
Safety interlock (SAFETY INTERLOCK)
[12]
[12]
Start command active (START SIGNAL APPLIED)
[13]
[13]
Reversing (RUNNING IN REVERSE)
[14]
[14]
Thermal warning (THERMAL WARNING)
[15]
[15]
Hand mode active (DRIVE IN HAND MODE)
[16]
[16]
Auto mode active (DRIVE IN AUTO MODE)
[17]
[17]
Sleep mode (SLEEP MODE)
[18]
[18]
Output frequency lower than f
LOW
parameter 223 (F OUT < F LOW)
[19]
[19]
Output frequency higher than f
HIGH
parameter 224 (F OUT > F HIGH)
[20]
[20]
Out of frequency range (FREQ RANGE WARN.)
[21]
[21]
Output current lower than I
LOW
parameter 221 (I OUT < I LOW)
[22]
[22]
Output current higher than I
HIGH
parameter 222 (I OUT > I HIGH)
[23]
[23]
Out of current range (CURRENT RANGE WARN.)
[24]
[24]
Out of feedback range (FEEDBACK RANGE WARN.)
[25]
[25]
Out of reference range (REFERENCE RANGE WARN.)
[26]
[26]
Relay 123 (RELAY 123)
[27]
[27]
Mains imbalance (MAINS IMBALANCE)
[28]
[28]
Control word 11/12 (CONTROL WORD 11/12)
[29]
[29]
Function:
Description of choice:
See description of [0] - [28] in
Analog/digital outputs
.
Control word bit 11/12
, relay 1 and relay 2 can
be activated via the serial communication. Bit 11
activates relay 1 and bit 12 activates relay 2.
If the parameter 556
Bus time interval function
becomes active, relay 1 and relay 2 will become cut off
if they are activated via the serial communication.
MG.40.A7.22 - VLT is a registered Danfoss trademark
93