Switching on the input
Switching on the input depends on the mains voltage
in question and on whether Quick discharge of the in-
termediate capacitor has been selected. The table
below states the waiting time between cut-ins.
Mains volt-
age
380 V
415 V
460 V
500 V
690 V
Without
quick dis-
charge
48 s
65 s
89 s
117 s
120 s
With quick
discharge
74 s
95 s
123 s
158 s
Acoustic noise
The acoustic interference from the frequency convert-
er comes from two sources:
1.
DC intermediate circuit coils.
2.
Integral fan.
Below are the typical values measured at a distance
of 1 m from the unit at full load:
VLT 5001-5006 200 - 240 V, VLT 5001-5011 380 - 500 V
IP 20 units:
IP 54 units:
50 dB(A)
62 dB(A)
VLT 5008-5027 200 - 240 V, VLT 5016-5102 380 - 500 V
IP 20 units:
61 dB(A)
IP 20 unit (VLT
5062-5102):
67 dB(A)
IP 54 units:
66 dB(A)
VLT 5032-5052 / 200 - 240 V
IP 20/NEMA 1 units:
70 dB(A)
IP 54 units:
65 dB(A)
VLT 5122-5302 / 380 - 500 V
IP 21/NEMA 1 units:
73 dB(A)
IP 54 units:
73 dB(A)
VLT 5352 / 380 - 500 V
IP 00/ IP 21 /NEMA 1 units:
80 dB(A)
IP 54 units:
80 dB(A)
VLT 5452-5552 / 380 - 500 V
All enclosure types:
83 dB(A)
VLT 5001-5011 / 525 - 600 V
IP 20/NEMA 1 units:
62 dB(A)
VLT 5016-5062 / 525 - 600 V
IP 20/NEMA 1 units:
66 dB(A)
VLT 5042-5352 / 525 - 690 V
IP 21/NEMA 1 units:
74 dB(A)
IP 54 units:
74 dB(A)
VLT 5402 / 525 - 690 V
All enclosure types:
80 dB(A)
VLT 5502-5602 / 525 - 690 V
All enclosure types:
83 dB(A)
Measured 1 meter from the unit at full load.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark
113
Special
conditions