Compact, Mains supply 3 x 525 - 600 V
According to international requirements
VLT type 5005
5006
5008
5011
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
6.4
9.5
11.5
11.5
I
VLT, MAX
(60 s) [A] (550 V)
7.0
10.5
12.7
12.7
I
VLT,N
[A] (575 V)
6.1
9.0
11.0
11.0
I
VLT, MAX
(60 s) [A] (575 V)
6.7
9.9
12.1
12.1
Output
S
VLT,N
[kVA] (550 V)
6.1
9.0
11.0
11.0
S
VLT,N
[kVA] (575 V)
6.1
9.0
11.0
11.0
Typical shaft output
P
VLT,N
[kW]
4
5.5
7.5
7.5
Typical shaft output
P
VLT,N
[HP]
5
7.5
10.0
10.0
Highl overload torque (160%):
Output current
I
VLT,N
[A] (550 V)
5.2
6.4
9.5
11.5
I
VLT, MAX
(60 s) [A] (550 V)
8.3
10.2
15.2
18.4
I
VLT,N
[A] (575 V)
4.9
6.1
9.0
11.0
I
VLT, MAX
(60 s) [A] (575 V)
7.8
9.8
14.4
17.6
Output
S
VLT,N
[kVA] (550 V)
5.0
6.1
9.0
11.0
S
VLT,N
[kVA] (575 V)
4.9
6.1
9.0
11.0
Typical shaft output
P
VLT,N
[kW]
3
4
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
4
5
7.5
10
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
6.2
9.2
11.2
11.2
I
L,N
[A] (600 V)
5.7
8.4
10.3
10.3
High overload torque ( 160 %):
Rated input current
I
L,N
[A] (550 V)
5.1
6.2
9.2
11.2
I
L,N
[A] (600 V)
4.6
5.7
8.4
10.3
Max. cable cross-section, power [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Max. pre-fuses
[-]/UL
1)
[A]
8
10
15
20
Efficiency
3)
0.96
0.96
0.96
0.96
Weight IP 20 EB
[kg]
10.5
10.5
10.5
10.5
Power loss at max.
load.
[W]
160
236
288
288
Enclosure
IP 20 / Nema 1
1. For type of fuses see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Design Guide
48
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark