26
MG.10.P2.22 - VLT is a registered Danfoss trademark
Force
Multiple
Coils
(0F
HEX
)
Description
Forces each coil (0X reference) in a sequence
of coils to either ON or OFF. When broadcast,
the function forces the same coil references
in all attached slaves.
Query
The query message specifies the coil
references to be forced. Coils are addressed
starting at zero. Coil 1 is addressed as 0.
Example of a request to set 10 coils starting at coil 1 (addressed as 0) from slave device 01.
Field Name
Example (HEX)
Slave Address
01
Function
0F
Coil Address HI
00
Coil Address LO
00
Quantity of Coils HI
00
Quantity of Coils LO
0A
Byte Count
02
Force Data HI (Coils 8-1)
FF
Force Data LO (Coils 10-9)
03
Error Check (CRC)
–
Response
The normal response returns the slave
address, function code, starting address, and
quantity of coils forced.
Field Name
Example (HEX)
Slave Address
01
Function
0F
Coil Address HI
00
Coil Address LO
00
Quantity of Coils HI
00
Quantity of Coils LO
0A
Error Check (CRC)
–
APPENDIX A
All manuals and user guides at all-guides.com