background image

1.1.3. Warning Against Unintended Start

1.

The motor can be brought to a stop by means of digital commands, bus commands,
references or a local stop, while the frequency converter is connected to mains.
If personal safety considerations make it necessary to ensure that no unintended start
occurs, these stop functions are not sufficient.

2.

While parameters are being changed, the motor may start. Consequently, the stop key
[STOP/RESET] must always be activated, following which data can be modified.

3.

A motor that has been stopped may start if faults occur in the electronics of the frequency
converter, or if a temporary overload or a fault in the supply mains or the motor con-
nection ceases.

1.1.4. Installation of Mechanical Brake (VLT 5000 and VLT 5000

FLUX)

Do not connect a mechanical brake to the output from the frequency converter before the relevant
parameters for brake control have been defined. (Select output in parameters 319, 321, 323 or
326 and cut-in current and frequency in parameters 223 and 225).

1.1.5. Use on Isolated Mains

See section RFI Switch in the Operating Instructions regarding use on isolated mains. It is im-
portant to follow the recommendations regarding installation on IT mains, including isolated delta
systems, since sufficient protection of the complete installation must be observed. Not taking care
using relevant monitoring for IT mains may result in damage.

Warning:

Touching the electrical parts may be fatal - even after the equipment has been dis-
connected from mains.
Also make sure that other voltage inputs have been disconnected, such as external
24 V DC, load-sharing (linkage of DC intermediate circuit), as well as the motor
connection for kinetic back-up.
D1 and D2 enclosures: Wait at least 20 minutes.
E1 enclosures: Wait at least 46 minutes.

1. General Information

VLT

®

 5000/6000/8000

High Power Installation Guide

4

 

 MI.90.J2.02 - VLT

®

 is a registered Danfoss trademark 

 

1

Summary of Contents for VLT 6000

Page 1: ...54 NEMA12 20 Gland Conduit Entry IP21 NEMA 1 and IP54 NEMA12 21 IP21 Drip shield installation D1 and D2 enclosure 22 Electrical Installation 23 Control Wires 23 Power Connections 25 Mains connection 3...

Page 2: ...1 General Information VLT 5000 6000 8000 High Power Installation Guide 2 MI 90 J2 02 VLT is a registered Danfoss trademark 1...

Page 3: ...on is desired set parameter 128 to data value ETR trip or data value ETR warning For VLT 6000 VLT 8000 and VLT 4000 set parameter 117 to data value ETR trip or data value ETR warning Note The function...

Page 4: ...t parameters for brake control have been defined Select output in parameters 319 321 323 or 326 and cut in current and frequency in parameters 223 and 225 1 1 5 Use on Isolated Mains See section RFI S...

Page 5: ...ion examples Electrical installation procedures short form Motor start As the units are available in different enclosure sizes depending on the rated output power the structure of the instruction is b...

Page 6: ...2 Preinstallation VLT 5000 6000 8000 High Power Installation Guide 6 MI 90 J2 02 VLT is a registered Danfoss trademark 2...

Page 7: ...he frequency converter is without built in fuses ensure that the external fuses are rated correctly 2 1 2 Receiving the Frequency Converter When receiving the frequency converter please make sure that...

Page 8: ...nclosure D1 1220 650 570 48 25 6 22 4 1730 650 570 53 9 25 6 22 4 Enclosure D2 1490 650 570 58 7 25 6 22 4 1730 650 570 68 1 25 6 22 4 Enclosure E1 1705 831 736 67 1 32 8 29 0 2197 840 736 86 5 33 1 2...

Page 9: ...uits or cable glands in IP 21 and IP 54 units Lifting bar to lift the unit rod or tube 20 mm 0 75 inch able to lift minimum 400 kg 880 lbs Crane or other lifting aid to place the frequency converter i...

Page 10: ...t Enclosure IP21 54 D1 and D2 Right Enclosure IP00 D1 D2 and E1 Illustration 3 4 Airflow direction and necessary space for cooling Enclosure IP21 54 E1 3 Installation VLT 5000 6000 8000 High Power Ins...

Page 11: ...osures Take the following position of the terminals into consideration when you design for cables access Illustration 3 5 Position of power connections Illustration 3 6 Position of power connections D...

Page 12: ...361 14 2 K 277 10 9 270 10 6 284 11 2 277 10 9 L 326 12 8 326 12 8 334 13 1 334 13 1 M 243 9 6 243 9 6 250 9 8 250 9 8 N 159 6 3 159 6 3 167 6 6 167 6 6 O 261 10 3 261 10 3 261 10 3 260 10 3 P 170 6 7...

Page 13: ...consideration when designing the cable access Illustration 3 7 IP00 enclosure power connection positions Illustration 3 8 IP00 enclosure power connection positions VLT 5000 6000 8000 High Power Instal...

Page 14: ...ns positions of disconnect switch Illustration 3 10 IP21 NEMA Type 1 and IP54 NEMA Type 12 enclosure power connection positions 3 Installation VLT 5000 6000 8000 High Power Installation Guide 14 MI 90...

Page 15: ...ower connection positions detail B Illustration 3 12 IP21 NEMA type 1 and IP54 NEMA type 12 enclosure power connection position of disconnect switch VLT 5000 6000 8000 High Power Installation Guide 3...

Page 16: ...es Each terminal allows use of up to 4 cables with cable lugs or use of standard box lug Earth is connected to relevant termination point in the drive Illustration 3 13 Terminal in details Illustratio...

Page 17: ...w The necessary airflow over the heat sink must be secured The flow rate is shown below Enclosure Door fan Top fan air flow Airflow over heatsink IP00 Chassis D1 and D2 255 m3 h 150 cfm 765 m3 h 450 c...

Page 18: ...2000 mm 176F1826 176F1825 176F1850 Table 3 3 Duct Kit Ordering Numbers Back cooling Using the channel from the back allows easy installation in for example control rooms The unit mounted to the backs...

Page 19: ...1 and IP54 NEMA 12 Units This only applies for D1 and D2 enclosures It must be considered where to install the unit Take the relevant points into consideration before you select the final installation...

Page 20: ...requency converters can also be installed on a pedestral Details can be found later in a later section of this Installation Guide and in the information included in the Pedestal kit D1 and D2 enclosur...

Page 21: ...4 NEMA12 Cables are connected through the gland plate from the bottom Remove the plate and plan where to place the entry for the glands or conduits Prepare holes in the marked area on the drawing The...

Page 22: ...quency converter is placed on the pedestal Illustration 3 24 Mounting of bottom plate E1 enclosure 3 1 7 IP21 Drip shield installation D1 and D2 enclosure To comply with the IP21 rating a separate dri...

Page 23: ...fieldbus from the top of the unit as shown on the pic ture below On the IP 21 NEMA 1 unit a cover plate must be removed Illustration 3 27 Top connection for fieldbus Installation of 24 Volt external D...

Page 24: ...re correct galvanic isolation type PELV on the control terminals of the frequency converter Relay output Torque 0 5 0 6 Nm 5 in lbs Screw size M3 No Function 1 3 Relay output 1 3 break 1 2 make See th...

Page 25: ...ions for details For protection of the frequency converter the recommended fuses must be used or the unit must be with built in fuses Recommended fuses can be seen in the Operating Instructions Always...

Page 26: ...enclosure D1 with disconnect fuse and RFI filter Illustration 3 30 Compact IP 00 Chassis with disconnect fuse and RFI filter enclosure D2 3 Installation VLT 5000 6000 8000 High Power Installation Guid...

Page 27: ...and IP 54 NEMA 12 with disconnect fuse and RFI filter enclo sure D2 Illustration 3 32 Compact IP 00 Chassis enclosure E1 VLT 5000 6000 8000 High Power Installation Guide 3 Installation MI 90 J2 02 VLT...

Page 28: ...00 Chassis with disconnect fuse and RFI filter enclosure E1 Illustration 3 34 Position of earth terminals IP00 3 Installation VLT 5000 6000 8000 High Power Installation Guide 28 MI 90 J2 02 VLT is a r...

Page 29: ...1 and IP 54 NEMA 12 enclosure E1 Illustration 3 36 Position of earth terminals IP21 NEMA type 1 and IP54 NEMA type 12 VLT 5000 6000 8000 High Power Installation Guide 3 Installation MI 90 J2 02 VLT is...

Page 30: ...th In the case of an earth fault a DC content may develop in the faulty current If ELCB relays are used local regulations must be observed Relays must be suitable for protection of 3 phase equipment w...

Page 31: ...M10 Brake 9 5 84 in lbs M8 Table 3 4 Torque for terminals 3 2 7 Shielded Cables It is important that shielded and armoured cables are connected in a proper way to ensure high EMC immunity and low emis...

Page 32: ...the brake resistor Size the brake cable cross section to match the brake torque See also Brake instructions MI 90 FX YY and MI 50 SX YY for further information regarding safe installation Please note...

Page 33: ...the DC bar is 25 metres 82 feet Load sharing enables linking of the DC intermediate circuits of several frequency converters Please note that voltages up to 1099 V DC may occur on the terminals Load...

Page 34: ...the correct current rating 3 2 14 External Fan Supply In case DC supplies the frequency converter or the fan must run independently of the power supply an external power supply can be applied The conn...

Page 35: ...suitable for use only with IP 00 Chassis frequency converters in Rittal TS8 IP 20 and UL and NEMA 1 and IP 54 and UL and NEMA 12 enclosures The duct work shown is for D1 and d2 enclosures The duct wor...

Page 36: ...e Rittal enclosure The template is referenced to the top left corner of the back panel Therefore the template may be used with any size back panel and both the 1800 mm and 2000 mm high enclosures Illu...

Page 37: ...Rittal TS8 enclosure remove and discard the rearmost 5 screws see illustration below located on the top cov er of the frequency converter The holes will be used to fasten the top ductwork with longer...

Page 38: ...partially as sembled with frequency converter bracket Temporarily install the top duct section as shown above Use the top duct cover piece to mark the enclosure top for the opening Alternatively the m...

Page 39: ...on the frequency converter The top duct work is attached to the frequency converter using existing holes on the top cover of the frequency converter Use the longer T25 screws provided with the kit in...

Page 40: ...duct collar is bolted to the duct using 3 T25 screws in the outermost holes of the brackets Tighten the screws to compress the gasket Illustration 4 23 Bottom ductwork pieces Illustration 4 24 Bottom...

Page 41: ...n 4 28 Bottom ductwork installed Illustration 4 29 Installation of bottom duct After the bottom ductwork has been posi tioned in place remove the three T25 screws from the outer holes in the mounting...

Page 42: ...Illustration 4 31 Bottom duct installed 4 Duct Work Cooling Kit for IP00 Units VLT 5000 6000 8000 High Power Installation Guide 42 MI 90 J2 02 VLT is a registered Danfoss trademark 4...

Page 43: ...the power components The frequency converter gland plate must be installed to provide adequate cooling air to the control components of the frequency converter via the door fan and to maintain the IP...

Page 44: ...artially assembled The completely assembled pedestal with ven ted front cover and two side covers installed Multiple frequency converters may be moun ted side by side The interior side closing plates...

Page 45: ...e Illustration 5 7 Three front screws Illustration 5 8 Frame D2 with pedestal installed VLT 5000 6000 8000 High Power Installation Guide 5 Installation on Pedestal IP 21 IP 54 Units MI 90 J2 02 VLT is...

Page 46: ...6 Start Up Check VLT 5000 6000 8000 High Power Installation Guide 46 MI 90 J2 02 VLT is a registered Danfoss trademark 6...

Page 47: ...our VLT fre quency converter Before you start please read the safety instructions on the first page of this instruction Note that the user is responsible that the VLT frequency converter motor and oth...

Page 48: ...and mains supply connections NOTE Only supplied on drives with an RFI filter 6 Mains connection 1 Check that the mains voltage matches the VLT frequency converter nominal input volt age 2 Ensure that...

Page 49: ...Choose parameters by means of and Press CHANGE DATA to change parameter value Data values are changed using and Press or to move the cursor Press OK to save parameter setting Set the desired language...

Page 50: ...T 8000 Press HAND START to start the motor Set motor speed in parameter 003 by VLT 5000 Set motor speed with the keys on LCP of VLT 6000 VLT 8000 and VLT 4000 Check if the direction of rotation is as...

Page 51: ...rter Remember to switch off the frequency converter before cleaning Checking connections Measuring the temperature on power connections with a thermal camera or infrared meter is recommended as a prev...

Page 52: ...8 Drawings VLT 5000 6000 8000 High Power Installation Guide 52 MI 90 J2 02 VLT is a registered Danfoss trademark 8...

Page 53: ...8 Drawings Mechanical detailed drawing VLT 5000 6000 8000 High Power Installation Guide 8 Drawings MI 90 J2 02 VLT is a registered Danfoss trademark 53 8...

Page 54: ...8 Drawings VLT 5000 6000 8000 High Power Installation Guide 54 MI 90 J2 02 VLT is a registered Danfoss trademark 8...

Page 55: ...VLT 5000 6000 8000 High Power Installation Guide 8 Drawings MI 90 J2 02 VLT is a registered Danfoss trademark 55 8...

Page 56: ...8 Drawings VLT 5000 6000 8000 High Power Installation Guide 56 MI 90 J2 02 VLT is a registered Danfoss trademark 8...

Page 57: ...VLT 5000 6000 8000 High Power Installation Guide 8 Drawings MI 90 J2 02 VLT is a registered Danfoss trademark 57 8...

Page 58: ...Connection 23 Floor Mounting 20 Fusing 25 I Installation Of 24 Volt External Dc Supply 23 Installation On Pedestal 43 Isolated Mains 4 It Mains 30 L Lifting 8 Load Sharing 33 M Mains Connection 34 Me...

Page 59: ...ded Cables 31 T Terminal Locations 11 Torque 31 U Unintended Start 4 Unpacking 7 W Weight And Dimensions 8 Wire Access 11 VLT 5000 6000 8000 High Power Installation Guide Index MI 90 J2 02 VLT is a re...

Reviews: