Set the desired language in parameter 001.
Set motor parameters according to the motor plate:
Motor power
Parameter 102
Motor voltage
Parameter 103
Motor frequency
Parameter 104
Motor current
Parameter 105
Rated motor speed
Parameter 106
Set frequency interval and ramp times.
Min. reference
Parameter 204
Max. reference
Parameter 205
Ramp up time
Parameter 207
Ramp down time
Parameter 208
Relay 1 function
Parameter 323
Relay 2 function
Parameter 326
6.1.5. Motor Start
VLT 5000
Press [START] to start the motor
VLT 4000
VLT 6000
VLT 8000
Press [HAND START] to start the motor
Set motor speed in parameter 003 by VLT 5000.
Set motor speed with the +/- keys on LCP of VLT 6000, VLT 8000 and VLT 4000.
Check if the direction of rotation is as shown in the display. It can be changed by swapping two
phases of the motor cable.
VLT 5000
Press [STOP] to stop the motor
VLT 4000
VLT 6000
VLT 8000
Press [OFF/STOP] to stop the motor
Select total or reduced Automatic Motor Adaptation (AMA) in parameter 107. For further descrip-
tion of AMA, please see the manual.
Press [START] to start the Automatic Motor Adaptation (AMA).
Press [DISPLAY/STATUS] to leave the Quick Menu.