1.5 Rating Tables
Ratings below are for the active filter. Drive related specifications can be found in the respective Low Harmonic Drive
Instruction Manual.
Harmonic compensation values for the LHD filters are approximate. Variations due to tuning for frame sizes and associated
drives may occur.
Model number
AAF006
A120
LHD filter
only
AAF006
A190
AAF006
A210
LHD filter
only
AAF00
6A250
AAF006
A310
AAF006
A330
AAF006
A400
Frame
D
E
F
E
Total
Current
[A]
120
190
210
250
310
330
400
Peak
Current
[A]
300
475
625
775
775
825
1000
Overload
60 s every 10
min
[%]
No overload
110
No overload
110
110
No overload
110
LHD built-in CT rating
[A]
500
NA
1000
NA
NA
1500
NA
Overcurrent indication
[% s]
Overcurrent trip level
[A pk]
554
554
1030
1030
1030
1818
1818
DC overcurrent
[A]
285
285
465
465
465
750
750
LCL Capacitor current trip
[A]
22
22
34
34
34
58
58
Damping resistor temperature
(° F
[
°
C])
239 [115]
239 [115]
239 [115]
239 [115]
239 [115]
239 [115]
239 [115]
Table 1.3 Product Related Specifications
The filter will automatically limit output to avoid overcurrent tripping.
Typical average switching frequency
3.0–4.5 kHz
Excessive switching frequency trip limit
6.0 kHz
Voltages
DC voltage maximum reference
790 V DC
Inrush circuit enabled
370 V DC
Inrush circuit disabled
395 V DC
Undervoltage disable
402 V DC
Undervoltage warning
423 V DC
Undervoltage re-enable (reset)
442 V DC
Start permissive
821 V DC
Overvoltage warning
850 V DC
Overvoltage trip
855 V DC
Temperatures
Heatsink over-temperature enable (automatic derating begins.)
185° F [85° C]
Heatsink over-temperature trip
221° F [105° C]
Heatsink under-temperature warning
32° F [0° C]
Damping resistor heatsink over-temperature enable (automatic derating begins.)
221° F [105° C]
Damping resistor heatsink over-temperature trip
239° F [115° C]
Power card over-temperature
154.4° F [68° C]
Power card under-temperature
-4° F [-20° C]
Ground fault alarm
50%
Table 1.4 Trip Points