8.2.5 Power Card Mounting Plate
1.
Remove the control assembly mounting bracket
in accordance with procedure.
2.
The power card mounting plate can be removed
with the power card still mounted, if so desired. If
the power card is to be removed, remove it in
accordance with the power card procedure.
3.
To remove the power card mounting plate with
the power card attached, unplug connectors
MK102, MK105, MK107, MK109, and MK112.
4.
Remove the nut (0.30 in [7 mm]) attaching the
MK102 ring lug to the power card mounting
plate.
5.
Note the position of the red and white cables
from the FU4 and FU5 fuse block for reassembly.
Unplug the cables.
6.
Remove the power card mounting plate by
removing seven (0.32 in [8 mm]) nuts.
Reinstall in the reverse order of this procedure. The ring
lug for the wire assembly that connects to power card
connector MK102 attaches to the right mounting stud on
the top of the power card mounting plate. See
for torque tightening values.
E-Frame Sizes Disassembly a...
VLT Advanced Active Filter AAF006 D and E Frames Service Manual
MG90Z122 - VLT
®
is a registered Danfoss trademark
8-5
8
8