7.
Use the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
130B
T771.10
Q1 My Personal Menu
Q2 Quick Setup
Q3 Function Setups
Q5 Changes Made
13.7% 13.0A 1(1)
Quick Menus
Illustration 3.4
8.
Select language and press [OK]. Then enter the
motor data in parameters 1-20/1-21 through 1-25.
The information can be found on the motor
nameplate. The entire quick menu is shown in
1-20 Motor Power [kW]
or
1-21 Motor
Power [HP]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
130B
T772.10
Q2
0.0 Hz 0.00kW 1(1)
Motor Setup
1 - 21 Motor Power [kW]
4.0
kW
Illustration 3.5
9.
For best results, skip
1-28 Motor Rotation Check
at
this time until basic programming is complete.
This will be tested following basic set-up.
10.
3-41 Ramp 1 Ramp Up Time
is recommended as
60 seconds for fans or 10 seconds for pumps.
11.
3-42 Ramp 1 Ramp Down Time
is recommended
as 60 seconds for fans or 10 seconds for pumps.
12.
For
4-12 Motor Speed Low Limit [Hz]
enter the
application requirements. If these values are
unknown at this time, the following values are
recommended. These values will ensure initial
frequency converter operation. However, take any
precautions necessary to prevent equipment
damage. Make sure that the recommended values
are safe to use for functional testing before
starting the equipment.
Fan = 20Hz
Pump = 20Hz
Compressor = 30Hz
13.
In
4-14 Motor Speed High Limit [Hz]
enter the
motor frequency from
1-23 Motor Frequency
.
14.
Leave
3-11 Jog Speed [Hz]
(10Hz) at the factory
default (this is not used in initial programming).
15.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave
5-12 Terminal 27 Digital Input
at factory
default. Otherwise select
No Operation
. For
frequency converters with an optional Danfoss
bypass, no jumper wire is required.
16.
5-40 Function Relay
, leave at factory default.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
3.4 Automatic Motor Adaptation
Automatic motor adaptation (AMA) is a test procedure that
measures the electrical characteristics of the motor to
optimize compatibility between the frequency converter
and the motor.
•
The frequency converter builds a mathematical
model of the motor for regulating output motor
current. The procedure also tests the input phase
balance of electrical power. It compares the
motor characteristics with the data entered in
parameters 1-20 to 1-25.
•
It does not cause the motor to run or harm to
the motor
•
Some motors may be unable to run the complete
version of the test. In that case, select
Enable
reduced AMA
•
If an output filter is connected to the motor,
select
Enable reduced AMA
•
If warnings or alarms occur, see
•
Run this procedure on a cold motor for best
results
To run AMA
1.
Press [Main Menu] to access parameters.
2.
Scroll to parameter group 1-**
Load and Motor
.
3.
Press [OK].
4.
Scroll to parameter group 1-2*
Motor Data
.
5.
Press [OK].
6.
Scroll to
1-29 Automatic Motor Adaptation (AMA)
.
7.
Press [OK].
8.
Select
Enable complete AMA
.
Start Up and Functional Tes...
VLT
®
AQUA Drive
Operating Instructions
26
MG.20.M8.02 - VLT
®