5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing
•
Parameters associated with the terminal enable
the function
•
For proper frequency converter functioning, the
control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See
for control terminal parameter number and
default setting. (Default setting can change based on the
selection in
0-03 Regional Settings
.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group 5-**
Digital In/Out
and press [OK].
130B
T768.10
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
14.6% 0.00A 1(1)
Main Menu
Illustration 5.11
2.
Scroll to parameter group 5-1*
Digital Inputs
and
press [OK].
130B
T769.10
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
14.7% 0.00A 1(1)
Digital In/Out
5-**
Illustration 5.12
3.
Scroll to
5-10 Terminal 18 Digital Input
. Press [OK]
to access function choices. The default setting
Start
is shown.
5-1*
130B
T770.10
5-10 Terminal 18 Digital
Input
[
8
]] Start
14.7% 0.00A 1(1)
Digital Inputs
Illustration 5.13
5.4 International/North American Default
Parameter Settings
Setting
0-03 Regional Settings
to International or North
America changes the default settings for some parameters.
The next table lists those parameters that are effected.
Parameter
International
Default Parameter
Value
North American
Default Parameter
Value
0-03 Regional
Settings
International
North America
0-71 Date Format
YYYY-MM-DD
MM/DD/YYYY
0-72 Time Format
24h
12h
1-20 Motor Power
[kW]
See Note 1
See Note 1
1-21 Motor Power
[HP]
See Note 2
See Note 2
1-22 Motor Voltage 230V/400V/575V
208V/460V/575V
1-23 Motor
Frequency
20 - 1000Hz
60Hz
3-03 Maximum
Reference
50Hz
60Hz
3-04 Reference
Function
Sum
External/Preset
4-13 Motor Speed
High Limit [RPM]
See Note 3
1500RPM
1800RPM
4-14 Motor Speed
High Limit [Hz]
See Note 4
50Hz
60Hz
4-19 Max Output
Frequency
1.0 - 1000.0Hz
120Hz
4-53 Warning Speed
High
1500RPM
1800RPM
5-12 Terminal 27
Digital Input
Coast inverse
External interlock
5-40 Function Relay Alarm
No alarm
6-15 Terminal 53
High Ref./Feedb.
Value
50
60
6-50 Terminal 42
Output
100
Speed 4-20mA
14-20 Reset Mode
Automatic reset x 10 Infinite auto reset
About Frequency Converter P...
VLT
®
AQUA Drive
Operating Instructions