5-40 Function Relay
Option:
Function:
[24]
Ready, voltage OK
[25]
Reverse
[26]
Bus OK
[27]
Torque limit stop
[28]
Brake: No Brake War
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[31]
Relay 123
[32]
Mech brake ctrl
[33]
Safe stop active
[36]
Control word bit 11
[37]
Control word bit 12
[40]
Out of ref range
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus ctrl.
[46]
Bus ctrl, 1 if timeout
[47]
Bus ctrl, 0 if timeout
[51]
MCO controlled
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[120] Local ref active
[121] Remote ref active
[122] No alarm
[123] Start command activ
[124] Running reverse
[125] Drive in hand mode
[126] Drive in auto mode
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
100.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the high reference
value [RPM] for the motor
shaft speed and the high
feedback value, see also
5-58 Term. 33 High Ref./
Feedb. Value
.
6.2.6 AN-## Analog In/Out
Parameter group for configuring the analog input and
output.
6-00 Live Zero Timeout Time
Range:
Function:
10 s
*
[1 -
99 s]
Enter the Live Zero Timeout time period. Live Zero
Timeout Time is active for analog inputs, i.e.,
terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value
associated with the selected current input falls
below 50% of the value set in
6-12 Terminal 53 Low Current
,
or
6-22 Terminal 54
Low Current
for a time period longer than the time
set in
, the function
selected in
6-01 Live Zero Timeout Function
will be
activated.
How to program the adjustab...