6.2.4 Limits and Warnings
Parameter group for configuring limits and warnings.
4-11 Motor Speed Low Limit [RPM]
Range:
Function:
0 RPM
*
[0 - par.
4-13 RPM]
Enter the minimum limit for motor speed.
The Motor Speed Low Limit can be set to
correspond to the manufacturer’s
recommended minimum motor speed. The
Motor Speed Low Limit must not exceed
the setting in
4-13 Motor Speed High Limit [RPM]
Range:
Function:
1500.
RPM
*
[par. 4-11
- 60000.
RPM]
Enter the maximum limit for motor speed.
The Motor Speed High Limit can be set to
correspond to the manufacturer’s
maximum rated motor. The Motor Speed
High Limit must exceed the setting in
4-11 Motor Speed Low Limit [RPM]
. Only
4-11 Motor Speed Low Limit [RPM]
or
4-12 Motor Speed Low Limit [Hz]
will be
displayed, depending on other parameters
in the main menu, and depending on
default settings dependant on global
location.
NOTE!
Max. output frequency cannot exceed 10% of the carrier
frequency (
14-01 Switching Frequency
).
NOTE!
Any changes in
4-13 Motor Speed High Limit [RPM]
will reset
the value in
4-53 Warning Speed High
to the same value as
set in
4-13 Motor Speed High Limit [RPM]
Parameter group for configuring the digital input and
output.
5-01 Terminal 27 Mode
Option:
Function:
[0]
*
Input
Defines terminal 27 as a digital input.
[1]
Output
Defines terminal 27 as a digital output.
How to program the adjustab...