6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. The function set in
6-01 Live Zero Timeout Function
will be
activated if the input signal on terminal 53 or
54 is below 50% of the value in
6-12 Terminal 53 Low Current
,
or
6-22 Terminal
54 Low Current
for a time period defined in
. If several timeouts
occur simultaneously, the adjustable frequency
drive prioritizes the timeout functions as
follows:
1.
6-01 Live Zero Timeout Function
2.
8-04 Control Timeout Function
The output frequency of the adjustable
frequency drive can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to Jog Speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent
trip
[0]
*
Off
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max.
speed
[5]
Stop and
trip
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-11 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
6-14 Terminal 53 Low Ref./Feedb. Value
.
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V
*
[par. 6-10 -
10.00 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference/
feedback value set in
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
low voltage/low current set in
and
6-12 Terminal 53 Low
Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
50.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
high voltage/high current
value set in
and
6-13 Terminal
53 High Current
.
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[0.00 - par.
6-21 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value, set in
6-24 Terminal 54 Low Ref./Feedb. Value
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V
*
[par. 6-20 -
10.00 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference/
feedback value set in
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
low voltage/low current value
set in
and
6-22 Terminal 54
Low Current
.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100.000
N/A
*
[-999999.999 -
999999.999 N/A]
Enter the analog input scaling
value that corresponds to the
high voltage/high current
value set in
and
6-23 Terminal 54 High Current
.
How to program the adjustab...