Table 30: Start/Stop with Reversing and 4 Preset Speeds
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
e3
0b
b9
34
.1
1
Drive
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start
Parameter 5-11 Terminal 19 Digital Input
[10] Reversing*
Parameter 5-12 Terminal 27 Digital Input
[0] No operation
Parameter 5-14 Terminal 32 Digital Input
[16] Preset ref bit 0
Parameter 5-15 Terminal 33 Digital Input
[17] Preset ref bit 1
Parameter 3-10 Preset Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
*=Default value
Notes/comments:
D IN 37 is an option.
Wiring Configuration Examples
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
86 | Danfoss A/S © 2020.01