Torque characteristics (NO)
Starting torque (constant torque)
Maximum 110% for 60 s once in 10 minutes.
(1)
Overload torque (constant torque)
Maximum 110% for 60 s once in 10 minutes.
(1)
1
Percentage relates to the drive's nominal current.
Torque characteristics (HO)
Starting torque (constant torque)
Maximum 150/160% for 60 s once in 10 minutes.
(1)
Starting torque (constant torque)
Maximum 150/160% for 60 s once in 10 minutes.
(1)
1
Percentage relates to the drive's nominal current.
Torque rise time in FLUX (for 5 kHz fsw)
1 ms
Torque rise time in VVC+ (independent of fsw)
10 ms
9.4 Ambient Conditions
Enclosure
IP20/Chassis, IP21/Type 1, IP54/Type 12
Vibration test (standard/ruggedized)
0.7 g/1.0 g
Relative humidty
5%-95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
Aggressive environment (IEC 60068-2-43) H
2
S test
Class Kd
Aggressive gases (IEC 60721-3-3)
Class 3C3
Test method according to IEC 60068-2-43
H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
Maximum 55° C (131° F)
(1)
- at full continuous FC output current (HO)
Maximum 50° C (122° F)
(1)
- at full continuous FC output current (NO)
Maximum 45° C (113° F)
(1)
Minimum ambient temperature during full-scale operation
0 °C (32 °F)
Minimum ambient temperature at reduced speed performance
-10 °C (14 °F)
Temperature during storage/transport
-25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating
1000 m (3280 ft)
Maximum altitude above sea level with derating
3000 m (9842 ft)
EMC standards, Emission
IEC/EN 61800-3
EMC standards, Immunity
IEC/EN 61800-3
Energy efficiency class
IE2
(2)
1
For more information, see the Derating section in the design guide.
2
Determined according to IEC 61800-9-2 (EN 50598-2) at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
136 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...