9.6.8 Control Card, 24 V DC Output
Terminal number
12, 13
Maximum load
200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs
and outputs.
9.6.9 Relay Outputs
Programmable relay outputs
2
Maximum wire cross-section to relay terminals
2.5 mm
2
(12 AWG)
Minimum wire cross-section to relay terminals
0.2 mm
2
(30 AWG)
Length of stripped wire
8 mm (0.3 in)
Relay 01 terminal number
1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)
(1)
on 1–2 (NO) (Resistive load)
(2) (3)
400 V AC, 2 A
Maximum terminal load (AC-15)
(1)
1–2 (NO) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 1–2 (NO) (Resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 1–2 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
(1)
on 1–3 (NC) (Resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
(1)
1–3 (NC) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 1–3 (NC) (Resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 1–3 (NC) (Inductive load)
24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO)
24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
Relay 02 terminal number
4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)
(1)
on 4–5 (NO) (Resistive load)
(2) (3)
400 V AC, 2 A
Maximum terminal load (AC-15)
(1)
4–5 (NO) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 4–5 (NO) (Resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 4–5 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
(1)
on 4–6 (NC) (Resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
(1)
4–6 (NC) (Inductive load @ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 4–6 (NC) (Resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 4–6 (NC) (Inductive load)
24 V DC, 0.1 A
Minimum terminal load on 4–6 (NC), 4–5 (NO)
24 V DC 10 mA, 24 V AC 2 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1
IEC 60947 parts 4 and 5.
2
Overvoltage Category II
3
UL applications 300 V AC 2 A.
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
Specifications
Operating Guide | VLT® AQUA Drive FC 202
AQ275652274277en-000101 / 130R0708
140 | Danfoss A/S © 2020.01
Summary of Contents for VLT AQUA Drive FC 202
Page 1: ...Operating Guide VLT AQUA Drive FC 202 355 800 kW Enclosure Sizes E1h E4h...
Page 2: ......
Page 3: ......
Page 4: ......
Page 172: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 170 Danfoss A S 2020 01...
Page 173: ...Operating Guide VLT AQUA Drive FC 202 AQ275652274277en 000101 130R0708 171 Danfoss A S 2020 01...