5.1.1. Electrical Data:
380 - 500 Volt
VLT Type
P110
P132
P160
P200
Output current
[VAC]
HO NO HO
NO
HO
NO HO NO
Continuous (100/ 100%) [A]
400
212 260 260 315 315 395 395 480
Intermittent (150/ 110%) [A]
400
318 286 390 347 473 435 593 528
Continuous (100/ 100%) [A]
460/ 500
190 240 240 302 302 361 361 443
Intermittent (150/ 110%) [A]
460/ 500
285 264 360 332 453 397 542 487
Output kVA
Continuous (100/ 100%) [kVA]
400
147 180 180 218 218 274 274 333
Intermittent (150/ 110%) [kVA]
400
220 198 270 240 327 301 410 366
Continuous (100/ 100%) [kVA]
460
151 191 191 241 241 288 288 353
Intermittent (150/ 110%) [kVA]
460
227 210 287 265 361 316 431 388
Continuous (100/ 100%) [kVA]
500
165 208 208 262 262 313 313 384
Intermittent (150/ 110%) [kVA]
500
247 229 312 288 392 344 469 422
Typical Shaft Output
High Overload (150%) [kW]
400
110
132
160
200
Normal Overload (110%) [kW]
400
132
160
200
250
High Overload (150%) [HP]
460
150
200
250
300
Normal Overload (110%) [HP]
460
200
250
300
350
High Overload (150%) [kW]
500
132
160
200
250
Normal Overload (110%) [kW]
500
160
200
250
315
Max. Motor Cable Length
500 feet (150 m) shielded, 1000 feet (300 m)
unshielded
Output Voltage [%]
0-100% of the AC line voltage
Output Frequency [Hz]
0-450
Rated Motor Voltage [V]
400/460/500
Rated Motor Frequency [Hz]
50/60
Thermal protection during
operation
ETR for motor (Class 20)
Thermal protection during
operation
Deg C.
VLT trip
90
VLT trip
105
VLT trip
105
VLT trip
115
Switching on the Output
Unlimited
Ramp times [sec]
0.01 - 3600
5. General Specifications
VLT
®
Automation Drive FC 300
Operating Instructions High Power
112
MG.33.U1.02 - VLT
®