525 - 690 Volt
VLT Type
P200
P250
P315
P355
Max. Input Current [A]
550
245 299 299 355 355 408
381
453
Max. Input Current [A]
575
234 286 286 339 339 390
366
434
Max. Input Current [A]
690
240 296 296 352 352 400
366
434
Max. external pre-fuses
1)
[A]
400
500
600
700
Soft Charge Fuses
2)
AC [A]
(qty)
20 (3)
SMPS fuse
3)
[A]
4
AC Fan fuse
3)
[A]
4
Supply Voltage [V]
3 Phase, 525-690 ± 10%
Supply Frequency [Hz]
50/ 60
Power Factor
>0.90 for 525 V, >0.85 for 690 V
Efficiency
0.98
Power loss at rated max. load (690 V)
High Overload (150%) [W]
4275
4875
5185
5383
Normal Overload (110%) [W]
5156
5821
6149
6449
Enclosure
IP00, IP21/ NEMA 1 & IP54/ NEMA 12
Vibration Test [g]
0.7
Relative Humidity [%]
93%, +2%, -3% (IEC 68-2-3)
Ambient Temperature [de-
grees C]
-10 Deg C to 40 Deg C continuously, periodically
at +45 degrees C
-25 Deg C to +65/ 70 Deg C for storage/ transport
Adjustable Frequency Drive
Protection
Ground and short-circuit protection
Weight
5)
IP00/ Chassis [kg]
122.9
137.7
151.3
221
IP21/ NEMA 1 [kg]
136.3
151.3
164.9
263
IP54/ NEMA 12 [kg]
136.3
151.3
164.9
263
1) Bussman 170M6000 series. See fuse chart
2) Bussmann FWH-20A6F or exact equivalent, 3 per unit
3) Bussmann KTK-4 or exact equivalent, 1 per unit
4) Littlefuse KLK-15 or exact equivalent, 1 per unit
5) VLT with standard input option, no brake, no loadsharing
VLT
®
Automation Drive FC 300
Operating Instructions High Power
5. General Specifications
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
119