3.4.4. Installation on pedestal
The frequency converter can also be installed on the floor. A dedicated floor stand is designed for
that purpose. It can only be used for units produced after week 50, 2004 (serial number
XXXXXG504).
This section describes the installation of a pedestal unit available for the VLT series frequency
converters frames D1 and D2. This is a 200 mm high pedestal that allows these frames to be floor
mounted. The front of the pedestal has openings for input air to the power components.
The frequency converter gland plate must be installed to provide adequate cooling air to the
control components of the frequency converter via the door fan and to maintain the IP21/NEMA
1 or IP54/NEMA 12 degrees of enclosure protections.
There is one pedestal that fits both frames D1 and D2.
Required Tools:
•
Socket wrench with 7-17 mm sockets
•
T30 Torx Driver
Torques:
•
M6 - 4.0 Nm (35 in-lbs)
•
M8 - 9.8 Nm (85 in-lbs)
•
M10 - 19.6 Nm (170 in-lbs)
Kit Contents:
•
Pedestal parts
•
Instruction manual
Illustration 3.60: Drive on pedestal.
The kit contains a U-shaped piece, a vented
front cover, 2 side covers, two front brackets
and the required hardware to assemble See
the exploded view of the installation, illustra-
tion “Three front screws” (drawing
130BA647).
Illustration 3.61: Pedestal parts
3. How to Install
VLT
®
Automation Drive FC 300
Operating Instructions High Power
44
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark