4.1.3. Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and
follow the quick set-up procedure using LCP 102 (read table from left to right):
Press
Q2 Quick Menu
0-01 Language
Set language
1-20 Motor power
Set Motor nameplate power
1-22 Motor voltage
Set Nameplate voltage
1-23 Motor frequency
Set Nameplate frequency
1-24 Motor current
Set Nameplate current
1-25 Motor nominal speed
Set Nameplate speed in RPM
5-12 Terminal 27 Digital
Input
If terminal default is
Coast inverse
it is
possible to change this setting to
No
function
. No connection to terminal 27
is then needed for running AMA
1-29 Automatic Motor
Adaptation
Set desired AMA function. Enable com-
plete AMA is recommended
3-02 Minimum reference
Set the minimum speed of the motor
shaft
3-03 Maximum reference
Set the maximum speed of the motor
shaft
3-41 Ramp1 up time
Set the ramping up time with reference
to nominal motor speed (set in par.
1-25)
3-42 Ramp1 down time
Set the ramping down time with refer-
ence to nominal motor speed (set in par.
1-25)
3-13 Reference site
Set the site from where the reference
must work