X
2
and the main reactance X
h
. Select this option if an LC filter is
used between the drive and the motor.
FC 301:
The complete AMA does not include X
h
measurement
for FC 301. Instead, the X
h
value is determined from the motor
database. Par. 1-35
Main Reactance (X
h
)
may be adjusted to
obtain optimal start performance.
[2]
Enable reduced AMA Performs a reduced AMA of the stator resistance R
s
in the sys-
tem only.
Note:
•
For the best adaptation of the frequency converter, run AMA on a cold motor.
•
AMA cannot be performed while the motor is running.
•
AMA cannot be performed on permanent magnet motors.
NB!
It is important to set motor par. 1-2* Motor Data correctly, since these form part of
the AMA algorithm. An AMA must be performed to achieve optimum dynamic motor
performance. It may take up to 10 min, depending on the power rating of the motor.
NB!
Avoid generating external torque during AMA.
NB!
If one of the settings in par. 1-2* Motor Data is changed, par. 1-30 to 1-39, the
advanced motor parameters, will return to default setting.
3-02 Minimum Reference
Range:
Function:
0.000
Unit
*
[-100000.000 - par.
3-03]
The
Minimum reference
is the minimum value obtained by the
sum of all references.
Minimum reference
is only active if
Min -
Max
[0] is set in par. 3-00.
3-03 Maximum Reference
Range:
Function:
1500.00
0
*
[Par. 3-02 -
100000.000]
Enter the Maximum Reference. The Maximum Reference is the
highest value obtainable by summing all references.
The Maximum Reference unit matches:
•
The choice of configuration in par. 1-00
Configuration
Mode
: for
Speed closed loop
[1], RPM; for
Torque
[2],
Nm.
•
The unit selected in par. 3-01
Reference/Feedback
Unit
.
VLT
®
Automation Drive FC 300
Operating Instructions High Power
4. How to Programme
MG.33.U1.02 - VLT
®
is a registered Danfoss trademark
77