D. Operation keys and indicator lights (LEDs)
13 [Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE
Parameter 5-12 Terminal 27 Digital Input
has coast
inverse as the default setting. This setting means
that [Hand On] does not start the motor if there is
no 24 V to terminal 27.
14 [Off/Reset]: Stops the motor (off). If in alarm mode, the
alarm is reset.
15 [Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
Table 3.3 Legend to
, Section D
WARNING
HIGH VOLTAGE
Touching the frequency converter after pressing the [Off/
Reset] key is still dangerous, because the key does not
disconnect the frequency converter from the mains.
•
Disconnect the frequency converter from the
mains and wait for the frequency converter to
fully discharge. See the discharge time in
3.1.2 The Right-key Function
Press [
►
] to edit any of the 4 digits on the display
individually. When pressing [
►
] once, the cursor moves to
the first digit and the digit starts flashing as shown in
. Press the [
▲
] [
▼
] to change the value.
Pressing [
►
] does not change the value of the digits or
move the decimal point.
130BC440.10
Setup 1
Setup 1
Setup 1
Setup 1
Setup 1
Illustration 3.3 Right-key Function
[
►
] can also be used for moving between parameter
groups. When in
Main Menu
, press [
►
] to move to the first
parameter in the next parameter group (for example, move
from
parameter 0-03 Regional Settings
[0] International
to
parameter 1-00 Configuration Mode
[0] Open loop
).
3.2 Quick Menu
The
Quick Menu
gives easy access to the most frequently
used parameters.
1.
To enter
Quick Menu
, press [Menu] until the
indicator in display is placed above
Quick Menu
.
2.
Press [
▲
] [
▼
] to select either QM1 or QM2, then
press [OK].
3.
Press [
▲
] [
▼
] to browse through the parameters in
Quick Menu
.
4.
Press [OK] to select a parameter.
5.
Press [
▲
] [
▼
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
To exit, press either [Back] twice (or 3 times if in
QM2 and QM3) to enter
Status
, or press [Menu]
once to enter
Main Menu
.
Programming
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
13
3
3