1-16 High Speed Filter Time Const.
Range:
Function:
is too short, the control becomes
unstable.
1-17 Voltage filter time const.
Range:
Function:
Size
related
*
[ 0.01 - 1
s]
Reduces the influence of high
frequency ripple and system resonance
in the calculation of supply voltage.
Without this filter, the ripples in the
currents can distort the calculated
voltage and affect the stability of the
system.
4.2.3 1-2* Motor Data
This parameter group comprises input data from the
nameplate on the connected motor.
NOTICE
Changing the value of these parameters affects the
setting of other parameters.
1-20 Motor Power
Option:
Function:
[2]
0.12 kW - 0.16 hp
[3]
0.18 kW - 0.25 hp
[4]
0.25 kW - 0.33 hp
[5]
0.37 kW - 0.5 hp
[6]
0.55 kW - 0.75 hp
[7]
0.75 kW - 1 hp
[8]
1.1 kW - 1.5 hp
[9]
1.5 kW - 2 hp
[10]
2.2 kW - 3 hp
[11]
3 kW - 4 hp
[12]
3.7 kW - 5 hp
[13]
4 kW - 5.4 hp
[14]
5.5 kW - 7.5 hp
[15]
7.5 kW - 10 hp
[16]
11 kW - 15 hp
[17]
15 kW - 20 hp
[18]
18.5 kW - 25 hp
[19]
22 kW - 30 hp
[20]
30 kW - 40 hp
[21]
37 kW - 50 hp
[22]
45 kW - 60 hp
[23]
55 kW - 75 hp
[24]
75 kW - 100 hp
[25]
90 kW - 120 hp
[26]
110 kW - 150 hp
1-22 Motor Voltage
Range:
Function:
Size
related
*
[50 - 1000
V]
Enter the nominal motor voltage
according to the motor nameplate
data. The default value corresponds to
the nominal rated output of the unit.
1-23 Motor Frequency
Range:
Function:
NOTICE
This parameter cannot be changed
while the motor Is running.
Size
related
*
[ 20 -
500
Hz]
Select the motor frequency value from the
motor nameplate. For 87 Hz operation with
230/440 V motors, set the value according to
the nameplate data for 230 V/50 Hz. Adapt
parameter 4-14 Motor Speed High Limit [Hz]
and
parameter 3-03 Maximum Reference
to the 87
Hz application.
1-24 Motor Current
Range:
Function:
Size
related
*
[ 0.01 -
10000.00 A]
Enter the nominal motor current
value from the motor nameplate
data. This data is used for
calculating motor torque, motor
thermal protection, and so on.
1-25 Motor Nominal Speed
Range:
Function:
Size related
*
[50 - 60000
RPM]
Enter the nominal motor speed
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
1-26 Motor Cont. Rated Torque
Range:
Function:
Size
related
*
[ 0.1 -
10000
Nm]
Enter the value from the motor nameplate
data. The default value corresponds to the
nominal rated output. This parameter is
available when
is set to
[1] PM, non-salient
SPM
, that is, the parameter is valid for PM
and non-salient SPM motors only.
Parameter Descriptions
Programming Guide
MG06C602