3-16 Reference 2 Source
Option:
Function:
sum of these reference signals defines
the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
*
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
[20] Digital pot.meter
[32] Bus PCD
3-17 Reference 3 Source
Option:
Function:
Select the reference input to be used
for the first reference signal.
Parameter 3-15 Reference 1 Source
parameter 3-16 Reference 2 Source
, and
parameter 3-17 Reference 3 Source
define up to 3 different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11]
*
Local bus
reference
[20]
Digital pot.meter
[32]
Bus PCD
3-18 Relative Scaling Reference Resource
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select a variable value to be added to the
fixed value (defined in
parameter 3-14 Preset Relative Reference
).
The sum of the fixed and variable values
(labelled Y in
) is multiplied
by the actual reference (labelled X in
). This product is then
added to the actual reference (X+X*Y/100)
to give the resulting actual reference.
3-18 Relative Scaling Reference Resource
Option:
Function:
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
130BA059.12
Z
Illustration 4.6 Resulting Actual
Reference
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
4.4.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of
the 4 ramps (parameter group
3-4* Ramp 1
,
3-5* Ramp 2
,
3-6* Ramp 3
, and
3-7* Ramp 4
).
t
acc
t
dec
130BD379.10
P 3-*2
Ramp (X)
Down
Time (Dec)
P 4-14
High-limit
Hz
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
Time
P 3-*1
Ramp (X)Up
Time (Acc)
Illustration 4.7 Example of Ramp 1
3-40 Ramp 1 Type
Option:
Function:
Select the ramp type, depending on
requirements for acceleration/deceleration. A
linear ramp gives constant acceleration during
ramping. A sine 2 ramp gives non-linear
acceleration.
[0]
*
Linear
[2]
Sine 2
Ramp
S-ramp based on the values set in
parameter 3-41 Ramp 1 Ramp Up Time
and
parameter 3-42 Ramp 1 Ramp Down Time
.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
42
Danfoss A/S © 7/2015 All rights reserved.
MG06C602