[51]
External
interlock
This function makes it possible to give an
external fault to the frequency converter. This
fault is treated in the same way as an
internally generated alarm.
[60]
Counter A
(Terminal 29 or 33 only) Input for increment
counting in the SLC counter.
[61]
Counter A
(Terminal 29 or 33 only) Input for decrement
counting in the SLC counter.
[62]
Reset
Counter A
Input for reset of counter A.
[63]
Counter B
(Terminal 29 or 33 only) Input for increment
counting in the SLC counter.
[64]
Counter B
(Terminal 29 or 33 only) Input for decrement
counting in the SLC counter.
[65]
Reset
Counter B
Input for reset of counter B.
[72]
PID error
inverse
Inverts the resulting error from the process
PID controller. Available only if
parameter 1-00 Configuration Mode
is set to
[6]
Surface Winder
or
[7] Extended PID Speed OL
.
[73]
PID reset I-
part
Resets the I-part of the process PID controller.
Equivalent to
parameter 7-40 Process PID I-part
. Available only when
parameter 1-00 Configuration Mode
is set to
[6]
Surface Winder
or
[7] Extended PID Speed OL
.
[74]
PID enable This option enables the extended process PID
controller. Equivalent to
. Available only if
parameter 1-00 Configuration Mode
is set to
[7]
Extended PID Speed OL
.
[150] Go To
Home
The frequency converter moves to the home
position.
[151] Home Ref.
Switch
Indicates the status of the home referenced
switch.
on
means that the home position is
reached,
off
means that the home position is
not reached.
[155] HW Limit
Positive
The positive hardware position limit is
exceeded. This option is active on the falling
edge.
[156] HW Limit
Negative
The negative hardware position limit is
exceeded. This option is active on the falling
edge.
[157] Pos. Quick
Stop Inv
Stops the frequency converter during
positioning with the ramp time that is set in
parameter 32-81 Motion Ctrl Quick Stop Ramp
.
This option is only effective when
parameter 37-00 Application Mode
is set to
[2]
Position Control
.
[160] Go To
Target Pos.
The frequency converter moves to the target
position. This option is only effective when
parameter 37-00 Application Mode
is set to
[2]
Position Control
.
[162] Pos. Idx
Bit0
Position index bit 0. This option is only
effective when
is set to
[2] Position Control
.
[163] Pos. Idx
Bit1
Position index bit 1. This option is only
effective when
is set to
[2] Position Control
.
[164] Pos. Idx
Bit2
Position index bit 2. This option is only
effective when
is set to
[2] Position Control
.
[165] Core
diameter
source
The core diameter source.
off
means core 1 is
selected, and
on
means that core 2 is
selected. This option is only effective when
parameter 37-00 Application Mode
is set to
[1]
Center winder
.
[166] New
diameter
select
Configures whether to select partial roll
diameter (
off
) or core diameter (
on
). This
option is only effective when
parameter 37-00 Application Mode
is set to
[1]
Center winder
.
[167] Reset
diameter
Resets the diameter. This option is only
effective when
is set to
[1] Center winder
.
[168] Winder jog
forward
Enables jog forward during center winding.
This option is only effective when
parameter 37-00 Application Mode
is set to
[1]
Center winder
.
[169] Winder jog
reverse
Enables jog reverse during center winding.
This option is only effective when
parameter 37-00 Application Mode
is set to
[1]
Center winder
.
[170] Tension on Enables tension PID control. This option is
only effective when
parameter 37-00 Application Mode
is set to
[1]
Center winder
.
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
*
Start Functions are described in parameter group
5-1*
Digital Inputs
.
5-11 Terminal 19 Digital Input
Option:
Function:
[10]
*
Reversing Functions are described in parameter group
5-1* Digital Inputs
.
5-12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described in parameter group
5-1* Digital Inputs
.
5-13 Terminal 29 Digital Input
Option:
Function:
[14]
*
Jog
Functions are described in parameter
group
5-1* Digital Inputs
.
[32]
Pulse time based
5-14 Terminal 32 Digital Input
Option:
Function:
[0]
*
No operation
Functions are described in parameter
group
5-1* Digital Inputs
.
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
51
4